Part of the SACE Tmax XT family, this 1000A withdrawable molded case circuit breaker delivers robust industrial power distribution. The moving part configuration requires an ABB XT7 fixed cradle for installation. It serves as a modern upgrade path, replacing discontinued SKHA36AT1000 models when utilized with the appropriate retrofit hardware. Equipped with an advanced Ekip Dip LS/I electronic trip unit, it provides adjustable long-time, short-time, and instantaneous protection.
Shunt Trip, Auxiliary Switch, Undervoltage Release, Motor Operator, Padlock Attachment, Key Lock, Mechanical Interlock, Rating Plugs, Fixed Part (Cradle)
Accessories
None (Moving Part Only)
Standards
CSA C22.2 No. 5, IEC 60947-2, UL 489
Approval
CCC, CE, CSA, cULus, EAC, KEMA, RINA, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Reverse Feed, 100% Rated, High Interrupting Capacity, Moving Part Only
Product FAQs
7 answers
What hardware is required to install this withdrawable circuit breaker?
The ABB XT7HU310DEWW000XXX is the moving part only. It requires an ABB SACE Tmax XT7 Fixed Part, also known as a cradle, for a complete withdrawable installation.
What does the H in the XT7H frame designation indicate?
The H signifies a High interrupting capacity. This frame provides up to 100kA at 240VAC and 65kA at 480VAC for demanding industrial power distribution systems.
What protection functions are included in the LSI trip unit?
The electronic Ekip trip unit provides adjustable Long-Time, Short-Time, and Instantaneous protection. This allows panel builders to fine-tune the trip curve for precise selective coordination with downstream devices.
What is the advantage of a withdrawable mounting style?
A withdrawable configuration allows the breaker to be quickly racked in or out of the fixed cradle. This enables rapid maintenance, testing, or replacement without disconnecting the primary power cables.
How does the withdrawable design enhance operator safety?
The withdrawable design allows the breaker to be racked out to a disconnected or test position. This provides physical isolation from the live bus before maintenance is performed on the circuit.
Can the XT7H series replace older GE Spectra breakers?
Yes, the ABB Tmax XT7 series is engineered as a modern upgrade path for discontinued General Electric molded case circuit breakers. It can replace legacy 1000A GE frames when paired with the appropriate retrofit hardware.
Can communication modules be added to this XT7 breaker?
Yes, the Ekip electronic trip units support optional communication modules for protocols like Modbus, Profibus, and Ethernet. These modules connect directly to the circuit breaker terminal box for integration into facility energy management systems.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.