| Brand | ABB / General Electric |
|---|---|
| Part Number | FBH26TE060RV |
| Series | FBH |
| Amperage | 60A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600Y/347VAC |
| Phase | 1 |
| AIC Rating | 200kA @ 240VAC, 100kA @ 480VAC, 35kA @ 600Y/347VAC |
| Frame Type | FB |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE Type AD Panelboards |
| Wire Gauge | 4-1/0 AWG |
| Max Wire | 1/0 AWG |
| Min Wire | 4 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm |
|---|---|
| Accessories | Line Connections for AD Panels, Load Lugs |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CE, CSA, HACR, UL, USCG |
| Temp Rating | 40C |
| Construction Features | Current Limiting, HACR Rated, Naval Rated |
The FBH26TE060RV is specifically designed for installation in GE Type AD panelboards. The RV suffix in the catalog number indicates it comes factory-equipped with the required line connections for AD panels and standard load lugs.
ABB acquired GE Industrial Solutions in 2018. As a result, Record Plus FB frame breakers like the FBH26TE060RV may arrive with either ABB or GE branding, but they are the exact same product in form, fit, and function.
In the GE Record Plus nomenclature, the H indicates a high interrupting capacity. For this FB frame breaker, it provides a 100kA interrupting rating at 480VAC and 200kA at 240VAC.
The factory-installed load lugs on the FBH26TE060RV accept copper or aluminum conductors ranging from 4 AWG to 1/0 AWG.
Yes, GE Record Plus breakers utilize a double-break rotary contact design. This provides current-limiting performance that enhances interruption capability and reduces let-through energy during a short circuit.
Yes, the Record Plus FB frame supports common internal accessories, such as auxiliary switches, undervoltage releases, shunt trips, and bell alarms, which are UL listed for field installation.
This breaker features a non-interchangeable, fixed thermal-magnetic trip unit. It provides standard Long-Time and Instantaneous protection functions for overload and short-circuit conditions.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.