| Brand | ABB / General Electric |
|---|---|
| Part Number | FBV26TE080RV |
| Series | FBV |
| Amperage | 80A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600Y/347VAC |
| Phase | 1 |
| AIC Rating | 65kA @ 240VAC, 35kA @ 480VAC, 22kA @ 600Y/347VAC |
| Frame Type | FB |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE A-Series AD / AD Plus Panelboards |
| Wire Gauge | 4-1/0 AWG (Cu/Al) |
| Max Wire | 1/0 AWG |
| Min Wire | 4 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm |
|---|---|
| Accessories | Line Connections for AD Panels, Load Lugs |
| Standards | CSA C22.2 No. 5, NEMA AB 1, UL 489 |
| Approval | CSA, HACR, UL |
| Temp Rating | -40C to 75C |
| Construction Features | Current Limiting, HACR Rated, Naval Rated, Reverse Feed |
This breaker is designed specifically for installation in GE A-Series AD and AD Plus panelboards. Always verify your panel labeling to ensure FB frame compatibility before installation.
The included lugs accept wire gauges from 4 AWG up to 1/0 AWG. The terminals are dual-rated for both copper and aluminum conductors, providing flexibility during installation.
The fixed thermal magnetic trip unit offers long-time and instantaneous (LI) protection. This combination safeguards electrical circuits against both gradual overloads and sudden short circuits.
It utilizes a bolt-on connection type. This provides a secure, vibration-resistant mechanical and electrical connection directly to the panelboard bus bars.
Yes, it is rated for up to 600VAC, making it suitable for 240V, 480V, and 600Y/347VAC commercial and industrial electrical systems.
The FB indicates that this breaker belongs to the FB frame size within the GE Record Plus family of molded case circuit breakers.
No, this model features fixed thermal and fixed magnetic trip settings. If your application requires adjustable trip curves, you will need to select a breaker with an electronic trip unit.
Yes, while it provides two poles for single-phase loads, it can be mounted in three-phase GE A-Series AD or AD Plus panelboards to feed 240V or 480V equipment.
Proper torque ensures a secure connection for the 4 to 1/0 AWG conductors. Under-tightening can lead to arcing and overheating, while over-tightening can damage the wire strands or the lug itself.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.