| Brand | ABB / General Electric |
|---|---|
| Part Number | TED136035 |
| Series | TED |
| Amperage | 35A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC, 500VDC |
| Phase | 3 |
| AIC Rating | 18kA @ 240VAC, 18kA @ 480VAC, 14kA @ 600VAC, 10kA @ 250VDC, 10kA @ 500VDC |
| Frame Type | TED |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE A-Series Panelboards, GE Spectra Series Panelboards |
| Wire Gauge | 14-2 AWG (Cu), 12-2 AWG (Al) |
| Max Wire | 2 AWG |
| Min Wire | 14 AWG (Cu), 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Lug Kits |
|---|---|
| Accessories | Lugs (TCAL12) |
| Standards | CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CE, CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Non-Interchangeable Trip, Reverse Feed, Quick-Make/Quick-Break, Trip-Free Mechanism |
This E-frame breaker is designed for bolt-on installation in GE A-Series and Spectra Series panelboards. It requires the appropriate mounting hardware kit depending on the specific panelboard interior.
This breaker comes with factory-installed TCAL12 lugs. They accept 14 to 2 AWG copper or 12 to 2 AWG aluminum conductors. Always consult the breaker label for exact torque specifications based on your wire size.
The WL suffix indicates that the circuit breaker is supplied with factory-installed line and load lugs. If the WL is omitted from the catalog number, the breaker is typically supplied with load lugs only.
Yes, the TED, TEB, and THED breakers all share the same E150 frame dimensions and mounting configurations. However, they have different interrupting capacities. Ensure the TED136035 meets or exceeds the available fault current requirements of your specific application before substituting.
Yes, GE E150 frame breakers, including the TED136035, are suitable for reverse feed applications.
Yes, the TED136035 is HACR rated, making it suitable for use with heating, air conditioning, and refrigeration equipment.
No, the TED136035 is a bolt-on molded case circuit breaker designed for panelboard mounting or individual enclosures. It is not designed for DIN rail installation.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.