Engineered for wet and damp locations requiring NEC compliance, this 20-amp double-pole unit provides essential personnel protection. It features an internal common trip and integrated self-testing to ensure continuous safety monitoring. Designed for residential and commercial applications, it mounts into GE A-Series panelboards, PowerMark Gold, and ABB ReliaHome load centers. This model serves as the modern, updated replacement for the discontinued THHQL2120GF version.
GE PowerMark Gold Load Centers, GE A-Series Panelboards, ABB ReliaHome Load Centers
Wire Gauge
14-8 AWG (Cu), 12-8 AWG (Al)
Max Wire
8 AWG
Min Wire
14 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LIG
Trip Function
Long-Time, Instantaneous, Ground Fault
Trip Adjustability
Fixed Thermal, Fixed Magnetic
Standards and features
Special Classification
GFCI
Available Options
Padlock Attachment
Accessories
Self-Test Feature
Standards
HACR, UL 489, UL 943
Approval
CSA, UL
Temp Rating
40C
Construction Features
HACR Rated, Common Trip, Quick-Make/Quick-Break, High Interrupting Capacity, Self-Test
Product FAQs
7 answers
Which load centers are compatible with the THHQL2120GFT circuit breaker?
This breaker is designed for use in GE PowerMark Gold load centers, GE A-Series panelboards, and ABB ReliaHome load centers that accept Q-Line plug-in breakers.
What level of ground fault protection does the THHQL2120GFT provide?
It provides Class A 5mA ground fault protection for personnel, which is required by the NEC for wet or damp locations such as bathrooms, kitchens, and outdoor receptacles.
Does the THHQL2120GFT feature automatic self-testing?
Yes. The T in the catalog number indicates it includes a self-test feature that periodically runs internal diagnostics to ensure the ground fault circuitry is functioning properly, meeting modern UL requirements.
What is the difference between the THQL2120GFT and the THHQL2120GFT?
The primary difference is the interrupting rating. The THQL2120GFT has a standard 10kAIC rating, while the THHQL2120GFT features a higher 22kAIC rating for systems with higher available fault current.
How is the neutral connection made on the THHQL2120GFT?
This breaker uses a pigtail neutral wire that must be connected directly to the neutral bus bar in the load center to ensure proper ground fault detection.
What wire sizes are accepted by the box lugs on this 20A GFCI breaker?
The terminals accept 14 to 8 AWG copper wire or 12 to 8 AWG aluminum wire.
Can the THHQL2120GFT replace the older THHQL2120GF?
Yes. The THHQL2120GFT is the direct, modern replacement for the discontinued THHQL2120GF. It adds the required automatic self-test functionality while maintaining the same physical footprint and 22kAIC rating.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.