Part of the Q-Line family, the THHQL22020ST1 is a 2-pole, 20A molded case circuit breaker built for commercial power distribution. It features a factory-installed 120VAC shunt trip for remote shutdown capabilities. This plug-on breaker installs into GE PowerMark Gold load centers and A-Series panelboards, accepting 14-8 AWG copper wire. Rated for 22kAIC at 240VAC, it provides reliable thermal-magnetic protection and is HACR rated for HVAC motor loads.
GE PowerMark Gold Load Centers, GE A-Series Panelboards
Wire Gauge
14-8 AWG (Cu), 12-8 AWG (Al)
Max Wire
8 AWG
Min Wire
14 AWG (Cu) / 12 AWG (Al)
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Fixed
Standards and features
Available Options
Auxiliary Switch, Padlock Attachment
Accessories
Shunt Trip (120VAC)
Standards
HACR, UL 489
Approval
CSA, UL
Temp Rating
60C to 75C
Construction Features
HACR Rated, Common Trip
Product FAQs
6 answers
Which GE panels accept the THHQL22020ST1 breaker?
It is compatible with GE PowerMark Gold load centers and GE A-Series panelboards. It snaps into standard 1-inch Q-Line bus connections.
What function does the ST1 suffix provide on this breaker?
The ST1 designation means this breaker is equipped with a 120VAC shunt trip. This allows for remote tripping of the breaker when a 120V signal is applied to the accessory leads, commonly used for emergency stop or fire alarm integration.
How does the THHQL series differ from standard THQL breakers?
THHQL breakers provide a higher maximum interrupting capacity of 22kAIC at 240VAC, compared to the standard 10kAIC rating of THQL models. This makes them suitable for commercial applications or residential services with higher available fault currents.
What are the acceptable wire gauges for the THHQL22020ST1 terminals?
The box lugs accommodate 14 to 8 AWG copper conductors or 12 to 8 AWG aluminum conductors. Ensure proper torque specifications are followed during installation.
Can this breaker replace a standard THHQL22020?
Yes, it will physically fit and provide the same 20A thermal-magnetic protection and 22kAIC rating. However, the ST1 version includes a shunt trip accessory. If your system does not require remote tripping, the standard THHQL22020 is the direct replacement.
Does this breaker provide GFCI or AFCI protection?
No, the THHQL22020ST1 features standard thermal-magnetic trip functions for overload and short-circuit protection. It does not include ground fault or arc fault circuitry.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.