ABB / General ElectricTKMA836600WL
Quantity
Re-Certified
Quantity
ABB / General ElectricTKMA836600WL
ABB / General ElectricTHKMA836600WL
ABB / General ElectricTHKMA836600
| Brand | ABB / General Electric |
|---|---|
| Part Number | TKMA836600-R |
| Series | TKMA |
| Amperage | 600A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC |
| Phase | 3 |
| AIC Rating | 42kA @ 240VAC, 30kA @ 480VAC, 22kA @ 600VAC, 20kA @ 250VDC |
| Frame Type | TKMA |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE A-Series Panelboards, GE Switchboards, Motor Control Centers |
| Wire Gauge | (3) 3/0 AWG - 500 kcmil (Al/Cu) |
| Max Wire | 500 kcmil |
| Min Wire | 3/0 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Adjustable Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Motor Operator, Lug Kits |
|---|---|
| Accessories | Load Lugs (TCAL81) |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB-1, UL 489 |
| Approval | CSA, HACR, IEC, UL |
| Temp Rating | 40C |
| Construction Features | Interchangeable Trip Unit, HACR Rated |
This 600A K-frame breaker is designed for installation in GE A-Series panelboards, GE switchboards, and motor control centers that accept bolt-on connections.
The factory lugs accommodate three conductors per phase, with a wire range of 3/0 AWG to 500 kcmil for both aluminum and copper conductors.
The LI designation indicates that the breaker provides Long-Time (L) and Instantaneous (I) protection. The Long-Time function protects against sustained overloads, while the Instantaneous function trips the breaker immediately during a severe short circuit.
This breaker features a thermal-magnetic trip unit with a fixed thermal element for overload protection and an adjustable magnetic element. This allows you to tune the instantaneous short-circuit pickup threshold to coordinate with other protective devices in your electrical system.
The main difference is their short-circuit interrupting capacity. The TKMA836600 is rated for 30kA at 480VAC, while the THKMA836600 is a higher-interrupting version rated for 35kA at 480VAC. Both share the same physical K-frame dimensions and bolt-on mounting.
ABB acquired GE Industrial Solutions in 2018. Depending on the production date, legacy K-frame breakers like the TKMA836600 may carry either GE or ABB branding. They are identical in form, fit, and function.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.