The ITE CE3B070 is a 3 Pole thermal magnetic molded case circuit breaker with a current rating of 70 Amps and a voltage rating of 600VAC. It has an interrupting rating of 100kAIC at 480V. The CE3B070 has a bolt-on connection type and includes long time and instantaneous trip functions.
What is the modern replacement for the ITE CE3B070 circuit breaker?
The ITE CE3B070 is a legacy CE frame breaker. The documented replacement path progresses through the CLE frame to the current Siemens CED63B070. The CED63B070 is mechanically and electrically interchangeable, but you must verify that the replacement meets your specific fault current requirements before installation.
What frame family does the CE3B070 belong to?
The CE3B070 is part of the legacy ITE and Siemens CE frame family. This is a current limiting molded case circuit breaker that shares physical dimensions with the standard 125A ED frame family, but features a specialized construction for higher interrupting capacities.
What does the 100kAIC at 480V interrupting rating indicate for this breaker?
The 100kAIC rating means the breaker can safely interrupt up to 100,000 amps of available fault current at 480VAC. This high interrupting capacity is characteristic of current limiting breakers used in commercial and industrial electrical distribution systems where high fault currents are present.
What are the advantages of the bolt-on connection for the CE3B070?
The bolt-on connection requires the breaker to be physically bolted to the panelboard busbars. This creates a highly secure, vibration resistant electrical and mechanical joint, which prevents arcing and overheating in demanding industrial environments compared to standard plug-in connections.
How does the thermal magnetic trip mechanism function in the CE3B070?
The thermal magnetic design provides dual protection. The thermal component utilizes a bimetallic strip that bends and trips the breaker during sustained overloads, providing long time protection. The magnetic component reacts to extreme current spikes, such as short circuits, to provide an instantaneous trip.
Can the 3 pole CE3B070 be installed in a single phase system?
Yes, a 3 pole breaker can be utilized in a single phase system by wiring the load across two of the three poles. The panelboard must be able to accommodate the physical footprint of a 3 pole bolt-on frame, and the installation must comply with local electrical codes.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.