Part of the legacy K-Frame series, this 250-amp molded case circuit breaker provides reliable thermal-magnetic protection for commercial and industrial applications. It installs into Square D I-Line panelboards and switchboards, utilizing a specific Phase A-B bus connection. Featuring an extra high interrupting capacity of 100kA at 240VAC, it ensures robust fault clearing.
HACR Rated, Extra High Interrupting Capacity, Phase A-B Connection
Product FAQs
6 answers
What panelboards accept the KC24250AB circuit breaker?
This breaker is designed exclusively for Square D I-Line panelboards and switchboards. It features a plug-on I-Line connection and cannot be installed in standard load centers or unit-mount configurations.
What does the AB suffix indicate on this breaker?
The AB suffix specifies the phase connection. It indicates that this 2-pole breaker is factory-configured to connect to the A and B phases on the I-Line bus stack.
Can the phase connection on the KC24250AB be changed in the field?
No, the phase connection on legacy K-Frame I-Line breakers is factory-set and cannot be modified. If your panel schedule requires a different phase arrangement, you must use a breaker with the corresponding suffix, such as AC or BC.
What is the modern replacement for the legacy KC24250AB?
The KC24250AB is part of the legacy K-Frame series. For modern panel upgrades, it is directly replaced by the PowerPact J-Frame series, specifically the JJA26250AB, which maintains the same 250A rating and A-B phase I-Line connection.
How does the trip unit function on the KC24250AB?
This breaker features a thermal magnetic trip unit with LI (Long-Time and Instantaneous) functions. The thermal protection is fixed at 250 amps, while the magnetic instantaneous trip is adjustable, allowing electricians to fine-tune short-circuit protection for specific loads.
How does the I-Line mounting system work for this breaker?
The KC24250AB snaps directly onto the stacked bus of an I-Line panelboard using built-in plug-on jaws. This design eliminates the need for separate mounting hardware or cabled bus connections, significantly speeding up installation.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.
Square D KC34200 - 200A 3 Pole Molded Case Circuit Breaker
I recommend this product
Rated 5 out of 5 stars
7/9/26
Breakers
great service!! I had bought 3 different breakers & there was one that i had to return. I called as soon as i realized it was wrong.( my fault) I had my return RMA in about 5 minutes of the phone call. Highly recommend!!