Designed for heavy residential loads, this 110A plug-on circuit breaker delivers reliable thermal-magnetic overcurrent protection. It is an ideal solution for feeding large subpanels or high-draw equipment. The unit installs into GE PowerMark Gold load centers, A-Series panelboards, and ABB ReliaHome enclosures. It features box lug terminals that accept 2-2/0 AWG wire. With a high interrupting capacity of 22kAIC at 120/240VAC, it includes an internal common trip and is HACR rated.
GE A-Series Panelboards, GE PowerMark Gold Load Centers, ABB ReliaHome Load Centers
Wire Gauge
2-2/0 AWG (Cu/Al)
Max Wire
2/0 AWG
Min Wire
2 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Fixed
Standards and features
Available Options
Shunt Trip, Auxiliary Switch, Padlock Attachment
Standards
HACR, UL 489
Approval
CSA, UL
Temp Rating
40C
Construction Features
HACR Rated, High Interrupting Capacity, Common Trip, Quick-Make/Quick-Break
Product FAQs
7 answers
What load centers are compatible with the THHQL21110?
This breaker is designed for use in GE A-Series Panelboards, GE PowerMark Gold Load Centers, and ABB ReliaHome Load Centers. It requires two full 1-inch spaces and cannot be used in slots restricted to half-inch THQP breakers.
What is the difference between the THHQL21110 and the standard THQL21110?
The THHQL21110 features a higher interrupting rating of 22kAIC, whereas the standard THQL21110 is rated for 10kAIC. Both share the same 1-inch per pole plug-in form factor and can be used in the same GE and ABB load centers, provided the panel requires or accepts a 22kAIC rating.
Why is this breaker listed under both ABB and General Electric?
ABB acquired GE Industrial Solutions in 2018. As a result, GE Q-Line breakers, including the THHQL series, are now manufactured by ABB but retain the original GE catalog numbers and backward compatibility with legacy GE load centers.
How should the conductors be terminated on the THHQL21110?
The box lugs accept 2 to 2/0 AWG copper or aluminum conductors. To comply with NEC 110.14(D), the lugs must be tightened using a calibrated torque tool to the exact specification printed on the breaker label, which is typically 45 lb-in for this wire range.
Can I use the THHQL21110 to replace a half-inch THQP breaker?
No. The THHQL21110 is a full-size Q-Line breaker that requires two standard 1-inch spaces, totaling 2 inches in width. THQP breakers are half-inch slimline breakers. You cannot fit a THHQL breaker into a single 1-inch space.
Can the THHQL21110 be used in a panel that specifies a 10kAIC main breaker?
Yes, a 22kAIC branch breaker like the THHQL21110 can generally be installed in a system with a lower fault current rating, but it will not increase the overall panel rating. However, you cannot use a 10kAIC breaker in a panel that requires a 22kAIC minimum. Always verify the required short-circuit current rating for your specific installation.
Does the THHQL21110 require a bolt-on connection?
No. The THHQL21110 is a plug-in circuit breaker. If your panel requires a bolt-on connection, you will need a THHQB or TQDL series breaker instead.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.