Tailored for specialized panel configurations, this 150-amp main breaker features a reverse handle design where the ON position faces the lugs. This two-pole component serves as the primary service disconnect for residential applications. The plug-on unit mounts securely into compatible Siemens and Murray load centers that demand a reverse-operating main. It replaces the legacy QN2150R to simplify maintenance. Delivering a standard 10kAIC rating, it utilizes proven thermal-magnetic technology.
Which load centers are compatible with the MPD2150R main breaker?
This 150A breaker is designed for installation in Siemens and Murray load centers that require a reverse-operating main breaker.
What does the reverse handle design on the MPD2150R mean for installation?
The reverse handle configuration means the ON position faces the lugs. This is specifically required for certain panelboard designs where the main breaker mounts in a reverse orientation.
Which legacy circuit breakers can the MPD2150R replace?
This breaker serves as a direct replacement for legacy QN2150R and Crouse-Hinds MD150H main breakers in compatible panels.
What wire sizes are accepted by the lugs on this breaker?
The terminal lugs are rated to accept 4 AWG to 300 kcmil copper or aluminum conductors. Ensure proper torque specifications are followed during installation.
What type of protection does the thermal-magnetic trip unit provide?
The fixed thermal-magnetic mechanism provides long-time response for overload conditions and an instantaneous trip function for short-circuit protection.
How does the MPD2150R connect to the panel bus?
It utilizes a plug-in connection, allowing the breaker to snap directly onto the bus bars of compatible Siemens or Murray load centers without the need for bolt-on hardware.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.