Schneider Electric BDL16040 1 Pole Circuit Breaker
The Schneider Electric BDL16040 is a 1 Pole thermal magnetic molded case circuit breaker with a current rating of 40 Amps and a voltage rating of 600Y/347VAC, 125VDC. It has an interrupting rating of 25kAIC at 240VAC. The BDL16040 has a unit mounting type and includes long time and instantaneous trip functions.
['Electrical Distribution Equipment', 'Industrial Control Panels']
Wire Gauge
14-3/0 AWG
Max Wire
3/0 AWG
Min Wire
14 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Adjustability
Fixed Thermal, Fixed Magnetic
Standards and features
Standards
RoHS, REACh, HACR
Approval
CE, EN/IEC, UL, CSA, NEMA, GB, NMX, CCC, EAC, NOM
Temp Rating
-25 to 70 °C
Product FAQs
9 answers
How is the BDL16040 circuit breaker mounted?
This PowerPacT B-frame breaker is a unit-mount device. It can be installed using the integrated DIN rail mounting capability or secured to a backpan with threaded fasteners.
What type of wire connections are included with the BDL16040?
This breaker comes standard with EverLink lugs on both the line and load ends. These lugs are designed to combat cable creep and maintain a durable, long-term connection without requiring periodic retightening.
Can the BDL16040 be used in DC electrical systems?
Yes, this 1-pole breaker is dual-rated for both AC and DC applications, supporting system voltages up to 125 VDC.
What is the short-circuit interrupting rating at 600Y/347 VAC?
While rated for 25 kA at 240 VAC, the BDL16040 provides a 14 kA interrupting capacity when applied at 600Y/347 VAC.
Is the BDL16040 rated for 100 percent continuous current?
No, this standard PowerPacT B-frame thermal-magnetic breaker is rated for 80 percent continuous current in accordance with NEC guidelines.
Can I add field-installable accessories to this PowerPacT B breaker?
Yes, the PowerPacT B-frame series supports a wide range of one-click, field-installable electrical accessories and auxiliaries to accommodate last-minute control panel design changes.
What safety features are built into the PowerPacT B-frame contacts?
All B-frame circuit breakers feature dual-break rotating contacts. This design reduces peak current and let-through energy during a short-circuit fault, enhancing overall equipment protection.
What does the 'L' in the BDL16040 catalog number represent?
In the Schneider Electric nomenclature, the 'L' indicates that the breaker is factory-equipped with EverLink lugs on both ends, as opposed to terminal nut connections.
Are the thermal and magnetic trip settings adjustable on the BDL16040?
No, this breaker features a fixed thermal-magnetic trip unit. The overload and short-circuit sensing elements are factory-sealed and cannot be adjusted in the field.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.