Schneider Electric HDL36150U43X 3 Pole Circuit Breaker
The Schneider Electric HDL36150U43X is a 3 Pole solid state molded case circuit breaker with a current rating of 150 Amps and a voltage rating of 600VAC, 250VDC. It has an interrupting rating of 25kAIC at 240VAC, 18kAIC at 480VAC. The HDL36150U43X has a feed-thru connection type and includes long time, short time and instantaneous trip functions.
What does the U43X suffix indicate on the HDL36150U43X?
The U43X suffix indicates that the breaker is equipped with a Micrologic 5.2 A (Ammeter) electronic solid-state trip unit. This provides adjustable Long-time, Short-time, and Instantaneous (LSI) overcurrent protection, along with an integrated ammeter display.
What trip functions are adjustable on the Micrologic 5.2 A trip unit?
The Micrologic 5.2 A trip unit provides LSI protection, allowing you to adjust the Long-time pickup and delay, Short-time pickup and delay, and Instantaneous pickup settings for precise selective coordination.
Does the HDL36150U43X use thermal-magnetic trip elements?
No, this breaker uses a solid-state electronic trip unit. Electronic trip units offer more precise and adjustable protection curves compared to traditional fixed thermal-magnetic breakers.
What type of mounting does the HDL36150U43X use?
This breaker features a feed-thru (unit mount) design, meaning it installs using mechanical lugs on both the line and load sides rather than plugging into a distribution bus.
Is this breaker compatible with Square D I-Line panelboards?
No, the HDL36150U43X is a unit-mount (feed-thru) breaker with lugs on both ends. It is not designed to plug into an I-Line bus. I-Line panelboards require a plug-in variant.
Can the HDL36150U43X be reverse fed?
Yes, this PowerPacT H-frame breaker is suitable for reverse-fed (back-fed) applications. The solid-state Micrologic trip unit does not restrict the breaker to forward-feeding only.
Does the HDL36150U43X include equipment ground fault protection?
No, this breaker features an LSI trip unit (Long-time, Short-time, Instantaneous). It does not include the Ground fault (G) protection function. If ground fault protection is required, a breaker with an LSIG trip unit is necessary.
Is the HDL36150U43X considered a Square D or Schneider Electric breaker?
Square D is a flagship brand of Schneider Electric. This PowerPacT H-frame breaker may be labeled under either the Square D or Schneider Electric brand name, but the physical product and HDL36150U43X catalog number are identical.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.