Rated for 10kAIC at 480Y/277VAC, this 32A miniature circuit breaker is part of Schneider Electric's Multi9 C60SP family. It clips onto standard 35mm DIN rails for quick integration into OEM control panels and replaces the legacy Merlin Gerin 24353. The 3-pole UL 1077 supplementary protector incorporates a thermal-magnetic C-curve trip mechanism, providing robust current-limiting performance and dependable protection against short circuits and overloads in industrial applications.
Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Rotary Handle, Terminal Shields, Busbar System
Standards
CSA C22.2 No 235, EN/IEC 60947-2, GB 14048.2, UL 1077
Approval
CCC, CE, CSA, IEC, RoHS, UR
Temp Rating
-30C to 70C
Construction Features
Current Limiting, Reverse Feed, RoHS Compliant, Mercury Free
Product FAQs
7 answers
What is the trip curve for the M9F22332 circuit breaker?
The M9F22332 features a C-curve trip profile. It is designed to trip between 7 and 10 times the rated current, making it suitable for standard industrial loads and control circuits.
How is the Schneider Electric M9F22332 mounted in a control panel?
This miniature circuit breaker is designed for standard 35mm DIN rail mounting. It features a clip-on mechanism for quick installation in OEM control panels and DIN rail systems.
Can I use Multi9 accessories with the M9F22332 breaker?
Yes, the M9F22332 is part of the Multi9 C60SP series and is compatible with standard Multi9 electrical accessories, including shunt trips, undervoltage releases, and auxiliary contacts.
Is the M9F22332 rated for use in UL 1077 applications?
Yes, this breaker is a UL 1077 recognized supplementary protector. It is also rated for IEC and EN 60947-2 applications.
What wire sizes are accepted by the terminals on this breaker?
The screw clamp tunnel terminals on the M9F22332 accept copper wiring ranging from 18 AWG to 2 AWG.
What specific series does the M9F22332 belong to?
The M9F22332 is part of the Schneider Electric Multi9 C60SP series of miniature circuit breakers.
Is this breaker suitable for isolation?
Yes, it features positive contact indication and is suitable for isolation according to the IEC and EN 60947-2 standard.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.