Part of the Multi9 C60SP series, this 4A miniature circuit breaker provides supplementary protection for industrial control panels and OEM equipment. It installs onto standard DIN rails and serves as a drop-in replacement for the legacy Merlin Gerin 24628. The unit is compatible with a wide range of padlock attachments and auxiliary switches. Rated for 14 kAIC at 120/240VAC, it features a D-curve trip profile designed to handle high inrush currents. It is UL 1077 recognized and RoHS compliant.
Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Rotary Handle, Terminal Shields, Busbar System
Accessories
Padlock Attachment (Provision)
Standards
CSA C22.2 No 235, EN/IEC 60947-2, GB 14048.2, UL 1077
Approval
CCC, CSA, IEC, UR
Temp Rating
-30C to 70C
Construction Features
Current Limiting, Reverse Feed, RoHS Compliant, Mercury Free
Product FAQs
7 answers
What is the trip curve for the M9F23104 circuit breaker?
This breaker features a D-curve trip profile. It is designed to trip between 10 and 14 times the rated current, making it ideal for loads with high inrush currents such as motors, transformers, and certain power supplies.
Is the Schneider Electric M9F23104 UL listed for branch circuit protection?
No, this device is UL 1077 Recognized as a supplementary protector. It is not a UL 489 listed branch circuit breaker. It must be used in applications where branch circuit protection is already provided upstream or is not required by code.
What accessories are compatible with this Multi9 supplementary protector?
The M9F23104 accepts a variety of field-installable Multi9 accessories. Compatible add-ons include auxiliary contacts, fault indicating contacts, shunt trips, and undervoltage releases.
What type of DIN rail is required for mounting?
This breaker is designed to snap directly onto a standard 35mm symmetrical DIN rail, commonly used in industrial control panels and automation enclosures.
Does this breaker provide positive contact indication for maintenance?
Yes, it features a green strip on the toggle that guarantees physical contact opening. This provides visual confirmation of safe downstream isolation for maintenance operations according to IEC/EN 60947-2 standards.
How much panel space does this 1-pole breaker occupy?
As part of the Multi9 modular system, this 1-pole breaker occupies a standard 18mm modular width on a DIN rail. This compact footprint helps conserve valuable space in high-density OEM control panels.
What international standards does the M9F23104 meet?
In addition to being UL 1077 Recognized, this multi-standard breaker complies with IEC/EN 60947-2, CSA C22.2 No. 235, and GB/T 14048.2, making it suitable for global OEM equipment designs.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.