Part of the advanced Multi9 family, this 10A supplementary protector provides exceptional reliability for industrial applications. The D-curve calibration is suited for equipment generating high starting currents, preventing unnecessary downtime. Mounting is accomplished via standard DIN rail connections in control panels. This model acts as an exact cross-reference for the obsolete Merlin Gerin 24658. Certified to UL 1077, it offers a 14kA interrupting capacity at 240VAC.
CSA C22.2 No 235, EN/IEC 60947-2, GB 14048.2, UL 1077
Approval
CCC, CSA, IEC, UR
Temp Rating
-30C to 70C
Construction Features
Supplementary Protection, Current Limiting, RoHS Compliant, Mercury Free
Product FAQs
8 answers
What is the trip curve for the M9F23210 circuit breaker?
The M9F23210 features a D-curve trip characteristic. It is designed to trip magnetically between 10 and 14 times the rated current, making it ideal for loads with high inrush currents such as motors and transformers.
Is the Schneider Electric M9F23210 rated as a branch circuit breaker?
No, the M9F23210 is a UL 1077 recognized supplementary protector. It is not intended for use as a UL 489 branch circuit breaker and must be used in conjunction with an appropriate upstream branch protection device.
How much DIN rail space does the M9F23210 require?
This 2-pole miniature circuit breaker requires 36mm of DIN rail space, which is equivalent to four 9mm pitches.
Can I add auxiliary contacts or shunt trips to the M9F23210?
Yes, the Multi 9 C60SP series is compatible with a range of electrical auxiliaries, including OF (open/closed status) contacts, SD (fault indicating) contacts, and MX (shunt trip) releases. These accessories mount directly to the side of the breaker.
Can the M9F23210 be used in reverse feeding applications?
Yes, the Multi 9 C60SP series supports reverse feeding. This allows power to be supplied from either the top or bottom terminals without compromising the protection capabilities of the breaker.
Does the M9F23210 provide a visual indication if it has tripped due to a fault?
Yes, the Multi 9 C60SP series features a positive contact indication with a green strip on the toggle. This ensures physical contact opening and allows for safe downstream operations.
What is the operating temperature range for the M9F23210?
The M9F23210 is designed to operate in ambient temperatures ranging from -30 degrees Celsius to 70 degrees Celsius.
What is the mechanical and electrical durability of the M9F23210?
The M9F23210 has a mechanical durability of up to 20,000 cycles and an electrical durability of up to 10,000 cycles.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.