Built for demanding commercial and industrial environments, the Siemens 3VA5120-4ED21-0AA0 is a 2-pole, 20A MCCB. It is equipped with a TM210 thermal-magnetic trip unit to safeguard critical circuits against overloads. This panel-mount breaker installs into Siemens P2 through P5 panelboards and enclosures. With the appropriate kit, it replaces legacy ED62B020 breakers. Featuring a 25 kAIC interrupt rating at 480VAC, the unit is HACR rated and current limiting for HVAC applications.
Auxiliary Switch, Alarm Switch, Shunt Trip, Undervoltage Release, Padlock Attachment, Motor Operator, Rotary Handle, DIN Rail Adapter
Accessories
None (Nut Keeper Plate)
Standards
HACR, IEC 60947-2, UL 489
Approval
CE, CSA, EAC, UL, VDE
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Reverse Feed
Product FAQs
7 answers
Can the 3VA5120-4ED21-0AA0 replace older Siemens ED frame breakers?
Yes, this 3VA51 frame breaker can replace legacy ED62B020 circuit breakers when installed with the appropriate retrofit mounting kit.
What type of trip unit is installed in the 3VA5120-4ED21-0AA0?
It features a TM210 thermal-magnetic trip unit with fixed long-time (thermal) and fixed instantaneous (magnetic) protection functions.
What is the instantaneous trip setting for the 3VA5120-4ED21-0AA0?
The magnetic instantaneous trip (Ii) is fixed at 300A, which is 15 times the 20A continuous current rating.
What is the maximum frame capacity for this Siemens 3VA5 breaker?
The 3VA5120-4ED21-0AA0 is built on the Siemens 3VA51 frame, which supports a maximum capacity of 125A.
Is the Siemens 3VA5120-4ED21-0AA0 rated for direct current (DC) applications?
Yes, this thermal-magnetic breaker is suitable for DC networks and carries a maximum voltage rating of 250V DC.
Can this Siemens 3VA5 breaker be reverse fed?
Yes, Siemens 3VA5 thermal-magnetic molded case circuit breakers are UL listed for reverse feed applications.
Is this 20A Siemens breaker HACR rated?
Yes, the 3VA5120-4ED21-0AA0 is HACR rated and current limiting, making it suitable for heating, air conditioning, and refrigeration equipment protection.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.8 out of 5 based on 8 reviews.