Siemens Q22020CT2NC Quadplex Miniature Circuit Breaker

  • 20A
  • 4 Pole
  • Plug-On
Siemens Q22020CT2NC
Quadplex Miniature Circuit Breaker
Brand Siemens
SKU Q22020CT2NC
Select Item Condition
Earn 124 SuperPoints
  • 20A
  • 4 Pole
  • Plug-On

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Siemens Q22020CT2NC - 20A Quadplex Miniature Circuit Breaker

New

$124.70 In Stock

Quantity

Similar Items

Description

Engineered for residential power distribution, the Siemens Q22020CT2NC quadplex breaker provides four 20A circuits within a two-pole footprint. This plug-on unit features a non-CTL design without a rejection clip. It mounts into older, pre-1968 ITE, Gould, and Siemens non-CTL load centers that accept QT breakers. Rated at 10kAIC, it utilizes thermal-magnetic trip technology.

Specifications

Key specifications
Brand Siemens
Series QT
Amperage 20A
Poles 4
Mounting Style Plug-On
Voltage 120/240VAC
Phase 1
AIC Rating 10kA @ 120/240VAC
Fit and installation
Frame Type Q
Terminal Type Lugs
For Use With Siemens Load Centers (Non-CTL), Older ITE/Gould Panels (Pre-1968)
Wire Gauge 14-6 AWG (Cu), 12-6 AWG (Al)
Max Wire 6 AWG
Min Wire 14 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed
Standards and features
Special Classification Quadplex
Available Options Padlock Attachment
Accessories Non-CTL (No Rejection Clip)
Standards HACR, SWD, UL 489
Approval CSA, UL
Temp Rating 40C
Construction Features HACR Rated, Non-CTL, Common Trip, Insta-Wire

Product FAQs

6 answers
What does the "NC" in the Q22020CT2NC catalog number mean?

The "NC" stands for Non-CTL (Circuit Total Limiting). This indicates the breaker is manufactured without a rejection clip, allowing it to be installed in older Siemens, ITE, or Gould load centers that lack CTL rejection features.

Can I use the Q22020CT2NC in a modern Siemens load center?

Generally, no. Modern Siemens load centers are designed for CTL breakers and include physical rejection features on the busbar that prevent the installation of Non-CTL breakers. The Q22020CT2NC is intended for older, pre-1968 panels or specific Non-CTL enclosures.

How are the circuits configured on the Q22020CT2NC quadplex breaker?

This quadplex breaker provides two independent 240V circuits in a two-inch footprint. It features a 2-pole 20A circuit on the inner poles and a separate 2-pole 20A circuit on the outer poles.

Are the inner and outer circuits on the Q22020CT2NC common trip?

Yes, the "CT2" designation indicates that both the inner 20A double-pole and the outer 20A double-pole circuits feature an internal common trip mechanism. If one leg of either 240V circuit overloads, both legs of that specific circuit will trip simultaneously.

Does the Q22020CT2NC require a rejection clip for installation?

No. Because it is a Non-CTL breaker, it does not have a rejection clip. This allows it to plug into any available full-size space in compatible older panels without being blocked by a notched busbar.

Can the Q22020CT2NC replace older ITE or Gould quad breakers?

Yes, this Siemens Non-CTL quad breaker is the direct replacement for older ITE and Gould 20/20A quadplex breakers used in pre-1968 load centers.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.