Siemens 3VA4120-4ED34-0AA0 SENTRON molded case circuit breaker is rated 20A at 600Y/347VAC with 3 poles and 3-phase operation. Interrupting ratings are 14kAIC at 600Y/347VAC and 25kAIC at 480Y/277VAC. It features thermal magnetic LI tripping with fixed thermal and fixed magnetic settings, standard protection and a load side lug connection. The 3VA frame mounts in a panelboard or switchboard and measures 5.1 in high, 3.0 in wide and 3.0 in deep. Conductor ranges are 14-8 AWG (Cu) and 12-8 AWG (Al), with an operating temperature range of -25C to 70C. Approvals are CE, CSA and UL; standards are CSA C22.2 No. 5, IEC 60947-2 and UL 489.
When should I select the 20A Siemens 3VA4120-4ED34-0AA0?
Select this 20A molded case circuit breaker when the circuit design calls for that current rating. Coordinate the selection with the load requirements and conductor ampacity.
How do I select this breaker based on available fault current?
Its interrupting rating is 14kAIC at 600Y/347VAC and 25kAIC at 480Y/277VAC. Compare available fault current at the installation point with the interrupting rating for the system voltage, and select a rating that meets or exceeds it.
Can I adjust the thermal or magnetic trip settings?
Both the thermal and magnetic trip settings are fixed. The LI thermal-magnetic trip provides time-delayed overload protection and instantaneous short-circuit protection, so select it where fixed trip settings meet the protection requirements.
What conductors can I terminate at the load-side lugs?
The load-side lug connection accepts 14-8 AWG copper or 12-8 AWG aluminum conductors. Select the wire size within the range for its conductor material, while also meeting the circuit's ampacity requirements.
What dimensions should I use when planning the installation layout?
The breaker is 5.1 in high, 3.0 in wide and 3.0 in deep. Use these dimensions when planning enclosure layout and space for conductor routing.
What operating temperature range should I check before installation?
The operating temperature range is -25C to 70C. Check the expected temperature at the breaker location against this range when selecting the installation environment.
Which standards should I check against project requirements?
The breaker carries CE, CSA and UL approvals, with standards CSA C22.2 No. 5, IEC 60947-2 and UL 489. These address circuit-breaker safety and performance requirements; use them when reviewing the project's required approvals and standards.
What does the 600Y/347VAC voltage rating mean for system selection?
The 600Y/347VAC slash rating applies to grounded-wye AC systems. Check both phase-to-phase and phase-to-ground voltage when selecting the breaker.
How should I use the phase and pole counts when selecting this breaker?
This breaker has 3 poles and a phase count of 3. Check both the circuit's phase count and the number of conductors requiring overcurrent protection when selecting the breaker.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 5 reviews.
Siemens 3VA4160-4ED34-0AA0 - 60A 3 Pole Molded Case Circuit Breaker
I recommend this product
Rated 5 out of 5 stars
7/27/26
SuperBreakers has you covered
SuperBreakers has you covered when you’re in a pinch and need breakers at the last minute. Their customer service is excellent, and the team consistently goes above and beyond to help. I highly recommend them!
RS
Rob S.
Verified Buyer
Reviewing
Siemens 3VA4150-6ED34-0AA0 - 50A 3 Pole Molded Case Circuit Breaker
I recommend this product
Rated 5 out of 5 stars
4/8/26
50 amp breaker
Very helpful and arrived quickly.
JB
Josh B.
Verified Buyer
Reviewing
Siemens 3VA4130-4ED24-0AA0 - 30A 2 Pole Molded Case Circuit Breaker
I recommend this product
Rated 5 out of 5 stars
3/5/26
Breakers
Exactly as described. Quick shipping.
JL
Jeff L.
Verified Buyer
Reviewing
Siemens 3VA4120-6ED14-0AA0 - 20A 1 Pole Molded Case Circuit Breaker
I recommend this product
Rated 5 out of 5 stars
2/11/26
Better than new
Great condition and fast shipping
KC
Ken C.
Verified Buyer
Reviewing
Siemens 3VA4150-4ED34-0AA0 - 50A 3 Pole Molded Case Circuit Breaker