Siemens FD63B080 SENTRON FD6 molded case circuit breaker is rated 80A, 600VAC and 500VDC, with 3 poles and 3-phase operation. UL 489 interrupting ratings are 22kA at 600VAC and 35kA at 480VAC. The FD-Frame breaker features unit mounting, line and load side lugs, standard protection and a thermal magnetic LI trip with fixed thermal and adjustable magnetic settings. It has UL and IEC approvals and WEEE, RoHS and REACh standards. The conductor range is 6 AWG - 350 MCM (Cu) and 4 AWG - 350 MCM (Al). Operating temperature is 40 °C. Dimensions are 4 in deep, 4.50 in wide and 9.5 in high.
How should I use the 80A rating when selecting the Siemens FD63B080?
The 80A rated current is the starting point for matching this molded case circuit breaker to the circuit load. Coordinate that rating with conductor ampacity and the circuit's protection requirements.
What voltage ratings should I use for AC and DC circuit selection?
The breaker is rated 600VAC and 500VDC. Use the rating for the circuit's supply type when checking system voltage; the AC and DC ratings are separate selection limits.
How do I check the interrupting rating against available fault current?
The UL 489 interrupting ratings are 35kA at 480VAC and 22kA at 600VAC. Compare available fault current at the installation point with the rating at the applicable voltage; it must not exceed that interrupting rating.
What does the thermal-magnetic LI trip do, and which setting is adjustable?
The thermal-magnetic LI trip provides long-time overload protection and instantaneous short-circuit protection. The thermal setting is fixed, while the magnetic setting is adjustable, allowing the instantaneous pickup to be selected for the circuit's protection requirements.
What copper and aluminum conductor sizes can the terminals accept?
The conductor range is 6 AWG to 350 MCM for copper and 4 AWG to 350 MCM for aluminum. Check both conductor material and size when selecting conductors for the terminals; aluminum has a different minimum size.
How are incoming and outgoing conductors connected?
The breaker has lug connections on both the line and load sides. Plan incoming supply conductors for the line-side lugs and outgoing circuit conductors for the load-side lugs.
What mounting method and dimensions should I use when planning the installation layout?
This is a unit-mount breaker measuring 9.5 in high, 4.50 in wide and 4.00 in deep. Use those dimensions to plan its physical footprint and conductor routing, and plan the mounting arrangement for unit mounting.
How does the three-pole configuration guide circuit selection?
The breaker has three poles and a three-phase configuration. Select it for a circuit requiring a breaker pole for each of the three phase conductors.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.