Built to protect circuits against overloads and short circuits, the Siemens NEG3B060L is a 60A, 3-pole molded case circuit breaker. Rated 240VAC, 480VAC and 600Y/347VAC, it interrupts 85kA, 35kA and 22kA respectively. The NEG series EG frame uses unit mounting and lug terminals. Fixed thermal magnetic trips provide long-time and instantaneous protection. It supports reverse feed, meets UL 489 and has CSA and UL approvals.
How should I use the 60A rating when selecting the Siemens NEG3B060L?
The 60A rating is the breaker's nominal current rating. Select it based on the circuit load, conductor ampacity and applicable circuit-sizing requirements, rather than treating 60A as the exact point at which it trips.
How do I check whether its interrupting rating is sufficient?
Compare available fault current at the installation point with the interrupting rating at your system voltage: 85kA at 240VAC, 35kA at 480VAC or 22kA at 600Y/347VAC. Available fault current must not exceed the applicable rating.
How does the thermal-magnetic trip work, and can I adjust it?
The thermal element provides long-time overload protection, while the magnetic element provides instantaneous short-circuit protection. Both elements are fixed, so select the breaker for the required protection rather than planning to adjust its trip settings.
What conductors can I terminate in the lugs?
The lugs accept copper or aluminum conductors from 8 AWG through 1/0 AWG. Use that range to check terminal acceptance, then select conductor size according to ampacity and installation requirements.
Can I feed the Siemens NEG3B060L in reverse?
Yes. Its reverse-feed construction permits power to enter from the opposite terminal end, giving you flexibility in supply routing. Keep the supply and load arrangement clearly marked during installation.
How does the three-pole configuration affect circuit wiring?
The three-pole configuration provides overcurrent protection for the three phase conductors of a three-phase circuit. The neutral connection is not applicable, so route the circuit neutral separately from the breaker's phase connections.
What does the 40C temperature rating mean for selection?
The 40C temperature rating is the ambient reference for the breaker's thermal performance. Consider the temperature at the breaker location when evaluating its 60A rating for the application.
Why do UL 489 and the UL and CSA approvals matter?
UL 489 covers molded case circuit breakers used for overcurrent protection. The UL and CSA approvals are relevant when your project requires those certifications for the circuit breaker.
What voltage systems can the Siemens NEG3B060L be selected for?
The Siemens NEG3B060L is rated for 240VAC, 480VAC and 600Y/347VAC. The 600Y/347VAC rating applies to grounded-wye systems, so match both the system voltage and grounding configuration when selecting it.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.