Built for standard circuit protection, the Siemens 3VA6325-6JP31-0AA0 is a 3-pole, 250A, 600VAC molded case circuit breaker. Interrupting ratings are 100kA at 240VAC, 65kA at 480VAC and 22kA at 600VAC. The 3VA6 series breaker has a 3VA63 frame, unit mounting and lug terminals. Electronic trip provides long-time, short-time and instantaneous functions, with adjustable thermal and magnetic settings over a 100-250A range. It has CE, CSA and UL approvals.
Alarm Switch, Auxiliary Switch, Motor Operator, Shunt Trip, Undervoltage Release
Standards
IEC 60947-2, UL 489
Approval
CE, CSA, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Reverse Feed
Product FAQs
9 answers
Can I adjust this 250A breaker for a lower-current application?
The Siemens 3VA6325-6JP31-0AA0 has a 250A rated current and a 100-250A adjustable trip range. This lets you select a trip setting within that range to match the circuit's protection requirements.
How do I select this breaker for the available fault current?
Its interrupting ratings are 100kA at 240VAC, 65kA at 480VAC and 22kA at 600VAC. Compare the available fault current at the installation point with the rating for the circuit voltage, and select the breaker only when that rating meets or exceeds the available fault current.
What protection functions does the LSI electronic trip include?
LSI includes long-time, short-time and instantaneous protection. Long-time protection addresses sustained overloads, short-time protection applies a delay to fault-current tripping, and instantaneous protection responds without an intentional delay. Consider these functions when planning protection coordination.
Can this breaker be reverse fed?
Yes, it has a reverse-feed feature, allowing power to enter through the opposite end from the conventional feed direction. This gives you flexibility when planning the incoming conductor routing.
What does the HACR rating mean for equipment selection?
HACR refers to heating, air-conditioning and refrigeration applications. The HACR rating is relevant when selecting circuit protection for that equipment; also match the breaker current, voltage and interrupting ratings to the application.
What dimensions should I use when planning the installation layout?
The breaker body is 9.80 in high, 5.40 in wide and 5.40 in deep, with unit-mount construction. Use these dimensions when laying out the mounting location and conductor routing.
What temperature range should I consider for the installation environment?
The temperature rating is -25C to 70C. Compare the expected installation temperatures with this range when selecting the breaker for the environment.
Which circuit breaker standards apply to this model?
This molded case circuit breaker carries UL 489 and IEC 60947-2 standards, along with CE, CSA and UL approvals. Use these standards and approvals when matching the breaker to the project's electrical approval requirements.
What does the three-pole configuration mean for circuit planning?
The Siemens 3VA6325-6JP31-0AA0 has three poles and a three-phase configuration. The pole count guides phase-conductor planning, while its 600VAC rated voltage is a separate criterion for evaluating the circuit's operating voltage.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 2 reviews.
Siemens 3VA6225-5HL31-0AA0 - 250A 3 Pole Molded Case Circuit Breaker
I recommend this product
Rated 5 out of 5 stars
10/2/25
Smooth Transaction, Great Seller, Solid product
I've ordered from SuperBreakers a couple times over the years. They have great customer service, knowledgeable employees, and I got my breaker in the expected timeline. I HIGHLY RECOMMEND this shop if you are a fellow circuit breaker enthusiast!
Siemens makes a reliable product. Y'all already know.