Siemens B315GFHH molded case circuit breaker is rated 15A and 208Y/120VAC, with 3 poles and a 65kAIC interrupting rating. It features a thermal magnetic trip, GFCI protection, panelboard mounting, a load side lug terminal connection and a pigtail neutral connection. This HBQDPF series breaker belongs to the BQ family. Its conductor range is 14-6 AWG, with a conductor temperature of 60/75 °C. Standards are RoHS and REACh.
How should I use the 15A rating when selecting the Siemens B315GFHH?
The 15A rated current guides load and conductor selection. Apply the circuit's load-sizing and conductor-ampacity requirements rather than treating 15A as an allowable continuous load in every application.
What circuit requirements should I check against its voltage rating and pole count?
This breaker has 3 poles and a 208Y/120VAC rating. Select it for a circuit requiring three-pole protection at that rated voltage.
How does the 65kAIC interrupting rating affect selection?
The 65kAIC rating describes the breaker's ability to interrupt short-circuit current. Available fault current at the installation point must not exceed that rating at the applicable rated voltage.
What protection does the GFCI feature add?
GFCI protection detects current imbalance associated with leakage outside the intended circuit path and interrupts the circuit. Choose this feature when ground-fault circuit-interrupter protection is required.
How does the thermal-magnetic trip respond to overcurrent?
The thermal element responds to sustained overloads, while the magnetic element responds rapidly to high short-circuit current. This combines overload and short-circuit protection in one breaker.
What does the pigtail neutral mean for installation?
The neutral connection uses a pigtail lead. Plan to connect that lead to the system neutral as part of the GFCI wiring.
What conductor sizes can I terminate on the load side?
The conductor range is 14-6 AWG, and the load-side connection uses a lug. Select a conductor within that range that also meets the circuit's ampacity requirements.
How does the 60/75 °C conductor temperature rating affect wire selection?
Use the 60/75 °C conductor temperature rating when checking allowable conductor ampacity. A conductor's higher insulation temperature rating alone does not permit using a higher ampacity at the connection.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.