Part of the Sentron family, this 900-amp molded case circuit breaker provides reliable long-time and instantaneous (LI) protection for demanding industrial environments. The unit-mount design integrates seamlessly into Siemens S4, S5, P4, and P5 panelboards, as well as SB-series switchboards and motor control centers. Featuring a high interrupting capacity of 100kA at 480VAC, this current-limiting ND-frame device ensures robust fault clearing without requiring external fusing.
Current Limiting, HACR Rated, Non-Interchangeable Trip
Product FAQs
10 answers
What equipment is compatible with the Siemens CND63B900 breaker?
This ND-frame breaker is designed for use in Siemens Sentron S4, S5, P4, and P5 panelboards, as well as SB1, SB2, and SB3 switchboards and compatible motor control centers.
What wire sizes are accepted by the lugs on the CND63B900?
The standard lugs for this 900A breaker accept four 250 to 500 kcmil conductors per phase, and are rated for both copper (Cu) and aluminum (Al) wire.
How does the trip unit operate on the CND63B900?
It features a thermal-magnetic trip unit with fixed thermal (long-time) protection and an adjustable magnetic (instantaneous) trip setting to coordinate with downstream devices.
Can the CND63B900 be used in DC applications?
Yes, this breaker is rated for use in direct current systems up to 500VDC, where it provides an interrupting capacity of 50kA.
What does the "C" in the CND63B900 catalog number indicate?
In the Siemens Sentron series, the "C" prefix designates a current-limiting circuit breaker with a high interrupting capacity. The CND63B900 provides up to 100kAIC at 480V and 65kAIC at 600V.
Can the CND63B900 be reverse fed?
Yes, because the CND63B900 features a factory-installed, non-interchangeable trip unit, it is suitable for reverse-feed applications in accordance with UL 489 requirements.
Is the trip unit on the CND63B900 interchangeable?
No, the CND63B900 comes with a factory-installed, non-interchangeable thermal-magnetic trip unit.
How does the CND63B900 connect to the panel bus?
The CND63B900 is a unit-mount, bolt-on circuit breaker. It fastens directly to the busbars in compatible Siemens panelboards and switchboards for a secure electrical connection.
What frame size is the Siemens CND63B900?
The CND63B900 is built on the Siemens Sentron ND frame, a robust molded case platform that supports amperages up to 1200A.
Does the CND63B900 provide ground fault protection?
No, the CND63B900 is equipped with a standard thermal-magnetic trip unit that provides long-time and instantaneous (LI) overcurrent protection. It does not include integrated ground fault protection.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.