Square D HDL36100U44X molded case circuit breaker is a 100A, 3-pole PowerPacT H-Frame breaker with an 80% continuous load rating. It has an adjustable electronic LSIG trip and a MicroLogic 6.2 A trip unit. Interrupting ratings are 25kA at 240VAC (UL 489), 18kA at 480VAC, 14kA at 600VAC and 20kA at 250VDC. This HACR rated breaker has unit mounting, line and load side lug connections, and a 14-3/0 AWG Cu/Al conductor range.
CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, UL 489
Approval
CE, CSA, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Reverse Feed
Product FAQs
9 answers
How should I size a continuous load for the Square D HDL36100U44X?
Use the 80% continuous load rating when sizing a continuous load against the 100A rated current. Do not treat the full 100A rating as the continuous-load allowance.
How do I select this breaker for AC voltage and available fault current?
The AC voltage ratings are 240VAC, 480Y/277VAC, 480VAC, 600Y/347VAC and 600VAC. Interrupting ratings are 25kA at 240VAC under UL 489, 18kA at 480VAC and 14kA at 600VAC. Select for the system voltage and ensure available fault current does not exceed the corresponding interrupting rating.
What protection does the MicroLogic 6.2 A electronic trip unit offer?
Its LSIG functions provide long-time, short-time, instantaneous and ground-fault protection. These functions address sustained overloads, short-circuit conditions and ground faults, guiding protection coordination for the circuit.
What current adjustment range can I use for protection settings?
The adjustable electronic trip range is 35-100A. Select a setting within that range based on conductor ampacity, load requirements and protection coordination, while keeping the 80% continuous load rating in the sizing calculation.
What conductors can I terminate, and how are the connections made?
The conductor range is 14-3/0 AWG for copper or aluminum, with lug connections on both the line and load sides. Select conductor material and size within that range, then verify ampacity separately for the circuit load and installation conditions.
What mounting method and dimensions should I plan around?
This unit-mount breaker measures 4.09 in wide, 6.4 in high and 3.4 in deep. Use those dimensions to plan the mounting layout and account separately for conductor routing and termination access.
What phase and frequency requirements should I check?
This is a 3-pole breaker rated for 3-phase service at 50/60Hz. Check phase configuration and operating frequency along with voltage and interrupting ratings during selection.
What does the HACR rating mean for equipment selection?
HACR refers to heating, air-conditioning and refrigeration applications. The HACR rating is relevant when equipment requirements call for a HACR-rated breaker; also check the required current, voltage and interrupting ratings.
What operating temperature range should I account for?
The operating temperature range is -25 to 70 °C. Evaluate the temperature at the breaker location, including heat from surrounding equipment, to keep operation within that range.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.