Schneider Electric / Square DBJA261001
Quantity
New
Quantity
Schneider Electric / Square DBJA261001
| Brand | Square D |
|---|---|
| Part Number | BJA261002 |
| Series | BJA |
| Amperage | 100A |
| Poles | 2 |
| Mounting Style | I-Line |
| Voltage | 208Y/120VAC, 240VAC, 480Y/277VAC, 480VAC, 600Y/347VAC, 250VDC |
| Phase | 1 |
| AIC Rating | 100kA @ 208Y/120VAC, 100kA @ 240VAC, 65kA @ 480Y/277VAC, 65kA @ 480VAC, 25kA @ 600Y/347VAC, 50kA @ 250VDC |
| Frame Type | BJA |
|---|---|
| Terminal Type | Lugs |
| For Use With | Square D I-Line Panelboards, Switchboards |
| Wire Gauge | 14-2/0 AWG (Al/Cu) |
| Max Wire | 2/0 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment |
|---|---|
| Accessories | Phase Connection AC |
| Standards | CSA C22.2 No 5, EN/IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CCC, CE, CSA, EAC, IEC, NOM, UL |
| Temp Rating | -25C to 70C |
| Construction Features | HACR Rated, Current Limiting, Visual Trip Indicator |
Yes. The PowerPacT B-frame series is the direct modern replacement for legacy Square D FA and FH frame I-Line circuit breakers. It maintains the same mounting space requirements, making it ideal for retrofitting existing I-Line panelboards.
This breaker utilizes an I-Line style plug-in connection. The line side features a shrouded plug-on jaw that mounts directly to the panelboard bus, while the load side uses mechanical lugs to terminate the outgoing conductors.
Yes. Because standard thermal-magnetic PowerPacT B-frame breakers lack line and load markings, they are suitable for reverse feeding. If used as a backfed main in an I-Line panelboard, it must be properly labeled to comply with National Electrical Code (NEC) requirements.
The J designates the interrupting rating tier within the Square D PowerPacT B-frame family. It indicates a high interrupting capacity, specifically rated for up to 100kA at 240VAC and 65kA at 480VAC.
No. This breaker is equipped with a fixed thermal-magnetic trip unit. Both the long-time overload protection and the instantaneous short-circuit protection thresholds are factory-set and cannot be adjusted in the field.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.