Skip to main content
Expedited shipping available at checkout

Square D HDA36100SA Molded Case Circuit Breaker

  • 100A
  • 3 Pole
  • I-Line
Square D HDA36100SA
Molded Case Circuit Breaker
Brand Square D
SKU HDA36100SA
Select Item Condition
Earn 752 SuperPoints
  • 100A
  • 3 Pole
  • I-Line

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Square D HDA36100SA - 100A 3 Pole Molded Case Circuit Breaker

Re-Certified

$752.38 In Stock

Quantity

Description

Built for long-time and instantaneous circuit protection, the Square D HDA36100SA is a 100A, 3-pole molded case circuit breaker rated 600VAC and 250VDC. This PowerPacT HDA-series breaker has an HDA frame and I-Line mounting. Its thermal-magnetic trip has fixed thermal and fixed magnetic settings. Interrupting ratings include 25kA at 240VAC and 14kA at 600VAC. Approvals include CE, CSA, IEC, NOM and UL.

Specifications

Key specifications
Brand Square D
Series HDA
Amperage 100A
Poles 3
Mounting Style I-Line
Voltage 240VAC, 480VAC, 600VAC, 250VDC
Phase 3
AIC Rating 25kA @ 240VAC, 18kA @ 480VAC, 14kA @ 600VAC, 20kA @ 250VDC
Fit and installation
Frame Type HDA
Terminal Type Lugs
For Use With Square D I-Line Panelboards and Switchboards
Wire Gauge 14-3/0 AWG (Cu/Al)
Max Wire 3/0 AWG
Min Wire 14 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Fixed Magnetic
Standards and features
Available Options Alarm Switch, Auxiliary Switch, Padlock Attachment, Shunt Trip, Undervoltage Release
Accessories 110-130VAC Shunt Trip
Standards CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, UL 489
Approval CE, CSA, IEC, NOM, UL
Temp Rating -25C to 70C
Construction Features HACR Rated

Product FAQs

10 answers
What circuit rating should I use when selecting the Square D HDA36100SA?

This is a 100A, 3-pole breaker for three-phase circuit protection. Select it according to the circuit's load, conductor ampacity and protection requirements, rather than current rating alone.

Can this breaker be used on AC or DC circuits?

The voltage ratings are 600VAC and 250VDC. Use the rating corresponding to the circuit type and verify that the circuit voltage does not exceed it.

How do I check the interrupting rating against available fault current?

The interrupting ratings are 25kA at 240VAC, 18kA at 480VAC, 14kA at 600VAC and 20kA at 250VDC. Compare the applicable rating with the available fault current at the installation point; the available fault current must not exceed that rating.

How does the thermal-magnetic trip work, and can I adjust it?

The thermal-magnetic trip provides long-time overload protection and instantaneous short-circuit protection. Both the thermal and magnetic settings are fixed, so select the breaker with those fixed protection characteristics in mind.

What conductor sizes and materials can I terminate?

The lug terminals accept copper or aluminum conductors from 14 AWG through 3/0 AWG. Choose a conductor within that range that also meets the circuit's ampacity and installation requirements.

What mounting method should I plan for?

This breaker uses I-Line mounting. Plan the installation around that mounting method rather than treating it as a generic mounting arrangement.

What dimensions should I use for layout planning?

The breaker measures 4.09 in wide, 6.40 in high and 3.40 in deep. Use these dimensions to account for the breaker body in the equipment layout.

What does the HACR rating mean for equipment selection?

HACR refers to heating, air-conditioning and refrigeration applications. The HACR rating is relevant when selecting circuit protection for equipment that calls for a HACR-rated breaker.

What temperature range should I consider for the installation location?

The temperature rating is -25C to 70C. Compare the expected installation temperatures with this range when selecting the breaker for the location.

How does the shunt trip support remote tripping?

The Square D HDA36100SA has a shunt-trip function that allows an external electrical signal to trip the breaker. This function supports control schemes that call for electrically initiated opening.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.