Square D HDL36100U43X molded case circuit breaker is a PowerPacT H-Frame unit rated 100A, with 3 poles and rated voltages of 600VAC and 250VDC. Interrupting ratings are 25kA at 240VAC, 18kA at 480VAC, 14kA at 600VAC and 20kA at 250VDC. The adjustable electronic LSI trip uses MicroLogic 5.2 A. Features include an 80% continuous load rating, HACR rating, unit mounting and line and load side lug connections for 14-3/0 AWG Cu/Al conductors.
CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, UL 489
Approval
CE, CSA, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Reverse Feed
Product FAQs
6 answers
How should I size continuous loads for the Square D HDL36100U43X?
The 100A current rating is paired with an 80% continuous-load rating. Size sustained loads to that continuous-load limit rather than treating 100A as the continuous-load allowance.
What protection and adjustment does the MicroLogic 5.2 A trip unit offer?
The adjustable electronic MicroLogic 5.2 A trip unit provides LSI protection: long-time, short-time, and instantaneous functions for overload and fault protection. Long-time pickup is adjustable from 0.25-1 x In, allowing the pickup threshold to be selected for the load and protection plan.
What conductor material and wire sizes can I use at the terminals?
The conductor range is 14-3/0 AWG for copper or aluminum, with lug connections on both the line and load sides. Select conductors within that range while also meeting the circuit's ampacity requirements.
What mounting style and dimensions should I use for mechanical layout?
This breaker uses unit mounting and measures 4.09 in wide, 6.4 in high, and 3.4 in deep. Use those dimensions and the mounting style when planning the mounting area and conductor routing.
Why does the HACR rating matter when selecting a breaker for HVAC equipment?
HACR means heating, air conditioning, and refrigeration. The HACR rating is relevant when the equipment's electrical requirements call for an HACR-rated circuit breaker.
What operating-temperature range should I consider for the installation location?
The operating-temperature range is -25 to 70 °C. Use that range when evaluating temperatures around the breaker during operation, including temperatures inside an enclosure.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.