The Square D HGA36100SA molded case circuit breaker protects circuits against overloads and short circuits. Rated 100A with 3 poles, it supports 240VAC, 480VAC, 600VAC, 250VDC and 500VDC. This PowerPacT HGA series breaker uses an H frame, I-Line mounting and lug terminals. Its fixed thermal-magnetic trip provides long-time and instantaneous protection, with CE, CSA, IEC, NOM and UL approvals.
CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, UL 489
Approval
CE, CSA, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated
Product FAQs
9 answers
How should I use the 100A rating when selecting the Square D HGA36100SA?
The 100A rated current is the basis for selecting this breaker for the circuit load. Coordinate that rating with the load requirements and conductor ampacity, rather than choosing by conductor terminal capacity alone.
How does the AC interrupting rating affect selection?
The AC interrupting ratings are 65kA at 240VAC, 35kA at 480VAC and 18kA at 600VAC. At the circuit voltage, select an interrupting rating that meets or exceeds the available fault current at the installation point.
Can I select this breaker for a DC circuit?
The DC voltage ratings are 250VDC and 500VDC, with a 20kA interrupting rating at each voltage. For DC selection, use the DC ratings and verify that the available fault current does not exceed 20kA.
Can I adjust the thermal or magnetic trip settings?
Both the thermal and magnetic trip settings are fixed. The thermal element provides long-time overload protection, while the magnetic element provides instantaneous response to high fault current. Select it where fixed trip characteristics meet the circuit's protection requirements.
What conductor sizes and materials can I terminate?
The lug terminals accept copper or aluminum conductors from 14 AWG through 3/0 AWG. Use this range to check terminal acceptance, then select conductor size for the circuit's ampacity requirements.
How do the pole count and neutral connection affect circuit planning?
This is a three-pole breaker for a three-phase circuit, with no neutral connection. Plan the phase conductors through the breaker and handle any required neutral connection separately.
What dimensions should I use for layout planning?
The breaker measures 4.09 in wide, 6.40 in high and 3.40 in deep. Use these dimensions to account for the breaker body in the equipment layout and plan conductor routing separately.
What does the HACR rating mean for equipment selection?
HACR means heating, air conditioning and refrigeration. The HACR rating is relevant when selecting protection for those equipment circuits; also check the equipment's voltage, current and interrupting-rating requirements.
How should I use the temperature rating when planning installation?
The temperature rating is -25C to 70C. Use that range when evaluating temperature conditions at the planned installation location, including heat within the enclosure.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.