Built for demanding industrial applications, the Square D HRL36100U31X is a 100A, 3-pole MCCB from the PowerPacT H-Frame family. It includes a factory-installed Micrologic 3.2 trip unit, offering adjustable long-time and instantaneous protection to optimize system coordination. This unit-mount breaker integrates into Square D NF panelboards, switchboards, and motor control centers using standard line and load lugs. It boasts an extra-high interrupting capacity of 200kAIC at 480VAC.
Line and Load Lugs Included, Micrologic 3.2 Trip Unit (Factory Installed)
Standards
CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval
CCC, CE, CSA, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
Current Limiting, HACR Rated, True RMS Sensing, 80% Rated, Double-Break Rotary Contact Structure, Extra High Interrupting Capacity
Product FAQs
7 answers
What type of trip unit is installed in the HRL36100U31X?
This breaker features the Micrologic 3.2 electronic trip unit. It provides adjustable dials for both long-time pickup and instantaneous (LI) trip settings to coordinate with your specific system requirements.
How is the HRL36100U31X mounted in a panel?
It is a unit-mount circuit breaker designed for feed-thru applications. It secures via mounting hardware and features line and load lugs rather than I-Line plug-on jaws.
Can I use the HRL36100U31X in a Square D I-Line panelboard?
No. The HRL36100U31X is a unit-mount breaker with lugs on both ends. For an I-Line panelboard, you must use an I-Line plug-on variant.
Do I need to purchase separate lugs for the HRL36100U31X?
No. This unit-mount breaker comes with factory-installed line and load lugs that accept 14 AWG to 3/0 AWG aluminum or copper wire.
What does the R in the HRL36100U31X part number indicate?
The R designates the interrupting rating class. In the PowerPacT H-frame series, R-class breakers provide an ultra-high current-limiting interrupting rating of 200kA at 480VAC and 100kA at 600VAC.
Does this breaker provide ground fault protection?
No. The Micrologic 3.2 trip unit provides long-time and instantaneous (LI) protection only. It does not include ground fault or short-time protection.
Can the HRL36100U31X be used in motor control centers?
Yes, this unit-mount breaker is suitable for use in motor control centers, switchboards, and enclosures that accept PowerPacT H-frame feed-thru breakers.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.