Square D QJP32100TM molded case circuit breaker is rated 100A, 3-pole and 240VAC, with a UL interrupting rating of 100kA at 240VAC. Part of the PowerPacT family, this Q-Frame breaker has an 80% continuous load rating and a 50/60Hz frequency rating. Its thermal magnetic trip has fixed thermal and fixed magnetic settings, an LI trip function, a magnetic hold setting of 1200A and a magnetic trip setting of 2400A. It uses unit mounting and has UL, CSA and NOM approvals.
EZ Meter-Pak Meter Centers, METER-PAK Metering Equipment
Wire Gauge
4 AWG-300 kcmil
Max Wire
300 kcmil
Min Wire
4 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Fixed Thermal, Fixed Magnetic
Standards and features
Standards
UL 489
Approval
CSA, NOM, UL
Temp Rating
40C to 70C
Product FAQs
10 answers
What electrical ratings should I check when selecting the Square D QJP32100TM?
This 100A, 3-pole breaker is rated for 240VAC, 3-phase service at 50/60Hz. Check the circuit voltage, phase, frequency and required current rating when selecting it.
Can I use the full 100A rating for a continuous load?
The continuous load rating is 80%, so size sustained loads within 80% of the 100A rated current. Apply that limit when selecting the breaker for continuous-duty circuits.
How do I use the interrupting rating when selecting this breaker?
The UL interrupting rating is 100kA at 240VAC. For that voltage application, select it where the available fault current does not exceed 100kA.
What protection does the thermal-magnetic trip provide, and can I adjust it?
The thermal-magnetic LI trip provides overload and instantaneous short-circuit protection. Both thermal and magnetic settings are fixed, so select it for applications that do not require adjustable trip settings.
How do the magnetic hold and trip settings affect selection?
The fixed magnetic settings are 1200A hold and 2400A trip. Use these values when evaluating instantaneous protection and coordination with other protective devices.
What conductor sizes can I terminate on this breaker?
The conductor range is 4 AWG-300 kcmil. Select conductors within that range while also meeting the circuit's ampacity requirements.
What terminal connections and tightening torque should I plan for?
The line side uses a terminal nut connection, and the load side uses a lug connection. Plan the terminations accordingly and tighten the terminals to 247.8 lb-in with a torque tool.
What mounting method and dimensions should I use for the installation layout?
This breaker uses unit mounting. Use its 6.47 in height, 4.50 in width and 3.93 in depth when planning the mounting layout and space allocation.
What operating temperature range should I consider?
Choose an installation environment within the breaker's 40 to 70 °C operating temperature range. Check the expected temperature at the breaker location during operation.
Which approvals should I check against project requirements?
The breaker carries UL, CSA and NOM approvals, with NOM-003-SCFI-2000 as its standard. Use these approvals when checking the project's certification requirements.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.