Engineered for commercial facilities, the Square D EJB14030EPD provides specialized 30mA ground fault equipment protection. This 30A, 1-pole breaker prevents electrical damage to industrial machinery by detecting low-level leakage currents. The device mounts into Square D NF panelboards using a secure bolt-on configuration. With an impressive 100kAIC rating at 120VAC, it handles severe fault conditions reliably. The breaker incorporates a Visi-Trip indicator and is HACR and HID rated.
CSA C22.2 No. 5, HACR, HID, NEMA AB 1, UL 1053, UL 489
Approval
CSA, cULus, NOM, UL
Temp Rating
40C
Construction Features
HACR Rated, HID Rated, Visual Trip Indicator
Product FAQs
6 answers
How much panel space does the EJB14030EPD require?
Although it is a 1-pole circuit breaker, it requires two pole spaces (1.96 inches wide) in the panelboard to accommodate the internal ground-fault circuitry.
What is the difference between this EPD breaker and a Class A GFCI?
This EPD (Equipment Protection Device) has a 30mA ground-fault trip threshold designed to protect equipment, such as heat trace cables, from damage. Class A GFCI breakers feature a highly sensitive 5mA threshold specifically required for personnel protection.
Which panelboards accept this E-frame breaker?
The bolt-on EJB14030EPD is engineered exclusively for use in Square D NF series panelboards.
How does the EJB frame compare to EDB and EGB breakers?
EJB models provide the highest interrupting ratings in the Square D E-frame family. They deliver 100kA at 120VAC and 65kA at 277VAC, whereas EDB and EGB breakers have lower fault-current withstand limits but share the exact same physical footprint.
How is the neutral connection handled on this breaker?
It is equipped with a pigtail neutral wire that must be tied directly to the panelboard neutral bar to power the internal ground-fault sensing equipment.
Can the EJB14030EPD replace lower-rated E-frame EPD breakers?
Yes. Because it utilizes the identical mounting footprint, this high-interrupting breaker can directly replace EDB14030EPD or EGB14030EPD breakers in applications requiring upgraded short-circuit ratings.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.9 out of 5 based on 12 reviews.