Built for industrial applications, the BGA260604 is a 60A, 2-pole PowerPacT B-Frame MCCB by Square D. It delivers reliable thermal-magnetic protection for systems up to 600Y/347VAC. Equipped with phase BC connections, this breaker mounts into Square D I-Line panelboards and switchboards. It is an exact substitute for discontinued FH26060BC and FA26060BC models. With an interrupting capacity of 35kA at 480V, this HACR-rated unit features a Visi-Trip indicator for quick troubleshooting.
CSA C22.2 No. 5, EN/IEC 60947-2, EN/IEC 60947-5-1, GB 14048.2, NEMA AB 1, NMX J-266, UL 489
Approval
CCC, CE, CSA, EAC, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Current Limiting
Product FAQs
8 answers
Is the BGA260604 a direct replacement for older Square D breakers?
Yes, the PowerPacT B-frame BGA260604 is a direct replacement for legacy F-frame breakers, specifically the discontinued FA26060BC and FH26060BC models. It fits the same I-Line panelboard mounting space without requiring blank fillers.
What type of panelboards are compatible with the BGA260604?
This breaker features an I-Line plug-on connection and is designed exclusively for use in Square D I-Line power distribution panelboards and switchboards.
What phase connection does the BGA260604 have?
The 4 at the end of the BGA260604 catalog number indicates it is factory-configured for a BC phase connection on the I-Line bus stack.
What does the G in the BGA260604 part number signify?
The G indicates the breaker's interrupting rating tier within the PowerPacT B-frame family. It provides a breaking capacity of 65kA at 240VAC, 35kA at 480VAC, and 18kA at 600Y/347VAC.
What wire sizes are accepted by the lugs on the BGA260604?
The factory-installed lugs accept wire gauges from 14 AWG up to 2/0 AWG and are rated for both aluminum and copper conductors.
Does the BGA260604 feature adjustable trip settings?
No, this thermal-magnetic breaker features fixed long-time (thermal) and fixed instantaneous (magnetic) trip settings.
Can the BGA260604 be used in direct current applications?
Yes, this breaker is rated for use in DC systems up to 250VDC, where it provides an interrupting rating of 20kAIC.
How does the I-Line mounting system work for this breaker?
The BGA260604 utilizes Square D's plug-on I-Line connection, which allows the line side of the breaker to snap directly onto the panelboard's bus stack. The load side features standard mechanical lugs for wire termination.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.