Built for demanding industrial environments, the Square D PLA34120 is a 3-pole, 1200A electronic trip molded case circuit breaker. As part of the PowerPacT P-Frame series, it provides robust equipment protection. Designed with an I-Line mounting style, this breaker installs into Square D I-Line panelboards and switchboards. Equipped with an ET 1.0I electronic trip unit, it delivers fixed long-time and adjustable instantaneous (LI) protection with a high 100kAIC interrupting rating at 480V.
HACR Rated, Current Limiting, True RMS Sensing, 80% Rated
Product FAQs
7 answers
What type of panelboards accept the PLA34120 circuit breaker?
The PLA34120 is an I-Line style plug-in breaker designed for use in Square D I-Line panelboards and switchboards that are configured to accommodate PowerPacT P-Frame breakers.
How much mounting space does this P-Frame breaker require in an I-Line panel?
The PLA34120 requires 9 inches of vertical mounting space in a compatible Square D I-Line panelboard or switchboard.
What does the "L" in the PLA34120 catalog number indicate?
The "L" designates the interrupting rating tier for this PowerPacT P-Frame breaker. It signifies a high interrupting capacity of 125 kA at 240V AC and 100 kA at 480V AC, compared to standard tiers like the "G" or "J" ratings.
Is the ET 1.0I trip unit on the PLA34120 field-interchangeable?
No. The basic ET 1.0I electronic trip unit is fixed and non-interchangeable. If you require field-interchangeable trip units, you must select a PowerPacT P-Frame breaker equipped with a MicroLogic trip unit.
What protection functions are included in the ET 1.0I trip unit?
The ET 1.0I is a basic electronic trip unit that provides LI functions, which include Long-Time (overload) and Instantaneous (short-circuit) protection. It does not include Short-Time or Ground Fault protection.
What replacement load-side lug kit is compatible with the PLA34120?
The standard mechanical lug kit for 1200A PowerPacT P-Frame breakers is the AL1200P24K. It accepts four 3/0 AWG to 500 kcmil aluminum or copper conductors per phase.
What is the difference between the PLA34120 and the PGA34120?
Both are 1200A, 3-pole, PowerPacT P-Frame I-Line breakers, but they feature different interrupting ratings. The PLA34120 has an "L" rating (100 kA at 480V AC), while the PGA34120 has a standard "G" rating (35 kA at 480V AC).
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.