Part of the Square D F-Frame series, the FC34015G is a 3-pole, 15A molded case circuit breaker designed for commercial power distribution. It delivers reliable thermal-magnetic protection with long-time and instantaneous trip functions. This unit mounts into Square D I-Line panelboards and switchboards. It is commonly replaced by the HJA36015, which requires checking external ground fault module compatibility. Rated for 65kAIC at 480VAC, it features a factory-installed ground fault shunt trip.
Load Side Lugs Included, Ground Fault Shunt Trip (Factory Installed)
Standards
CSA C22.2 No. 5, NEMA AB 1, UL 489
Approval
CSA, HACR, UL
Temp Rating
40C
Construction Features
Visual Trip Indicator, HACR Rated, High Interrupting Capacity
Product FAQs
8 answers
What panelboards are compatible with the FC34015G?
This breaker is designed exclusively for Square D I-Line panelboards and switchboards. It features an I-Line style plug-in connection for the line side.
What does the G suffix in the FC34015G catalog number indicate?
The G suffix indicates that the breaker includes a factory-installed ground fault shunt trip. It is designed to be used in conjunction with an external Square D ground fault sensor module, such as the GFM100FA.
Can I use this breaker to replace a standard FA or FH I-Line breaker?
Yes, the FC frame shares the same physical dimensions and I-Line mounting as FA and FH breakers, but offers a higher interrupting capacity of 65kA at 480V. However, ensure your application requires the G suffix ground fault shunt trip before substituting.
Is the FC34015G still manufactured, or is there a modern replacement?
The FC34015G is a legacy F-frame breaker. The modern equivalent is the PowerPact H-frame series, such as the HJA36015. However, because this specific breaker has a G suffix for external ground fault modules, you must verify compatibility with your existing ground fault system before upgrading.
How does the I-Line connection work on the FC34015G?
The breaker features a blow-on plug-in jaw connection on the line side that attaches directly to the I-Line busbar. The load side uses standard mechanical lugs for wire termination.
What wire sizes are accepted by the lugs on this breaker?
The factory-installed load side lugs accept 14 AWG to 1/0 AWG copper wire, or 12 AWG to 1/0 AWG aluminum wire.
Can the FC34015G be used in DC power systems?
Yes, this thermal magnetic breaker is rated for DC applications up to 250VDC, with an interrupting capacity of 10kA.
What type of trip unit does this breaker use?
It uses a fixed thermal magnetic trip unit with Long-Time and Instantaneous functions to protect against overloads and short circuits.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 2 reviews.