The Square D HGL36030SA is a 3 Pole thermal magnetic molded case circuit breaker with a current rating of 30 Amps and a voltage rating of 600VAC, 500VDC. It has an interrupting rating of 65kAIC at 240VAC, 35kAIC at 480VAC. The HGL36030SA has a unit mounting type and includes long time and instantaneous trip functions.
Industrial Control Panels, Switchboards, PowerPacT H-Frame Enclosures
Wire Gauge
14-3/0 AWG
Max Wire
3/0 AWG
Min Wire
14 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Fixed Thermal, Fixed Magnetic
Standards and features
Standards
RoHS, REACh, HACR
Approval
CE, UL, CSA, NEMA, NOM, IEC
Temp Rating
-25 to 70 °C
Product FAQs
7 answers
What does the SA suffix indicate on the HGL36030SA circuit breaker?
The SA suffix indicates that this PowerPacT H-frame breaker includes a factory-installed 110 to 130 VAC shunt trip release coil.
Can I field-install a shunt trip on a standard HGL36030 breaker instead of buying the HGL36030SA?
Yes, you can add a field-installable shunt trip to a standard PowerPacT H-frame breaker. The equivalent field-installable 110 to 130 VAC shunt trip accessory is catalog number S29386.
What is the recommended tightening torque for the lugs on the HGL36030SA?
The factory lugs require a tightening torque of 44 lb-in (5 N.m) for the accepted 14 to 3/0 AWG wire range.
Are the trip settings adjustable on the HGL36030SA?
No, this breaker uses a fixed thermal-magnetic trip unit. Both the long-time overload and instantaneous short-circuit trip points are factory-set and cannot be adjusted in the field.
What are the magnetic trip settings for the HGL36030SA?
The 30A thermal-magnetic trip unit has a fixed magnetic hold current of 350A and a fixed magnetic tripping current of 750A.
Can the HGL36030SA be reverse fed?
Yes, standard PowerPacT H-frame breakers with factory-sealed thermal-magnetic trip units, such as the HGL36030SA, are suitable for reverse-fed applications.
How is the HGL36030SA mounted in a panel?
This is a unit-mount circuit breaker. It is designed to be individually mounted to a backpan or mounting plate and uses feed-thru lugs for both line and load connections, rather than plugging into an I-Line bus.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.