Schneider ElectricJDA36250U31X
Quantity
New
Quantity
Schneider ElectricJDA36250U31X
| Brand | Square D |
|---|---|
| Part Number | JDM36250U33X |
| Series | JDM |
| Amperage | 250A |
| Poles | 3 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 600VAC |
| Phase | 3 |
| AIC Rating | 25kA @ 240VAC, 18kA @ 480VAC, 14kA @ 600VAC |
| Frame Type | JDM |
|---|---|
| Terminal Type | Lugs |
| For Use With | Industrial Control Panels, Switchboards, Motor Control Centers, Unit Mount Enclosures |
| Wire Gauge | 3/0 AWG - 350 kcmil (Al/Cu) |
| Max Wire | 350 kcmil |
| Min Wire | 3/0 AWG |
| Trip Technology | Electronic Trip |
|---|---|
| Trip Function Code | LSI |
| Trip Function | Long-Time, Short-Time, Instantaneous |
| Trip Adjustability | Adjustable |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Rotary Handle, Terminal Shields |
|---|---|
| Accessories | Line Side Lugs Included |
| Standards | CSA C22.2 No 5, HACR, IEC 60947-2, NEMA AB 1, NOM-003-SCFI-2000, UL 489 |
| Approval | CCC, CE, CSA, IEC, NOM, UL, UKCA |
| Temp Rating | -25C to 70C |
| Construction Features | HACR Rated, Current Limiting, Visual Trip Indicator, True RMS Sensing, Reverse Feed, Non-Interchangeable Trip, 80% Rated |
The "U33X" suffix indicates the breaker is equipped with a Micrologic 3.2 S electronic trip unit. This provides field-adjustable Long-Time, Short-Time, and Instantaneous (LSI) standard protection.
No, the JDM36250U33X is a unit-mount (bolt-on) circuit breaker designed for individual enclosures, switchboards, or industrial control panels. For an I-Line plug-in connection, you would need the I-Line equivalent, such as the JDA36250U33X.
The difference is the terminal configuration. The JDM36250U33X is equipped with line-side lugs and load-side terminal nuts, whereas the JDL36250U33X features standard lugs on both the line and load sides.
Yes, the solid-state Micrologic electronic trip unit allows you to adjust the long-time pickup, long-time delay, short-time pickup, short-time delay, and instantaneous trip settings to coordinate with your specific system requirements.
Yes, this PowerPacT J-Frame breaker is suitable for reverse-fed applications. Always verify with the specific equipment labeling and local NEC requirements before reverse feeding.
Yes, the PowerPacT J-Frame supports a variety of field-installable internal accessories, including shunt trips, undervoltage releases (UVR), and auxiliary switches. These are installed behind the accessory cover on the front of the breaker.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.