Built for industrial applications, the Square D LCP36300MT is a 3-pole, 300A molded case circuit breaker from the legacy L-Frame family. It provides reliable thermal-magnetic protection for demanding electrical systems. This bolt-on breaker installs into Square D switchboards, motor control centers, and enclosures. It serves as an exact replacement for older installations. Rated for 65kAIC at 480VAC, this unit features extra high interrupting capacity and includes load side lugs.

Specifications

Key specifications
Brand Square D
Series LCP
Amperage 300A
Poles 3
Mounting Style Bolt-On
Voltage 240VAC, 480VAC, 600VAC, 250VDC
Phase 3
AIC Rating 100kA @ 240VAC, 65kA @ 480VAC, 35kA @ 600VAC, 10kA @ 250VDC
Fit and installation
Terminal Type Lugs
For Use With Square D Switchboards, Motor Control Centers, Enclosures
Wire Gauge (1) 1 AWG-600 kcmil or (2) 1 AWG-250 kcmil (Al/Cu)
Max Wire 600 kcmil
Min Wire 1 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Adjustable Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch
Accessories Load Side Lugs Included, Plug-On Shroud
Standards CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval CSA, HACR, IEC, UL
Temp Rating 40C
Construction Features HACR Rated, High Interrupting Capacity

Product FAQs

6 answers
What types of equipment is the LCP36300MT designed to fit?

This legacy L-Frame breaker is designed for installation in Square D switchboards, motor control centers, and industrial enclosures.

What wire sizes are compatible with the lugs on this breaker?

The terminals accept either one 1 AWG to 600 kcmil conductor or two 1 AWG to 250 kcmil conductors per phase. The lugs are rated for both copper and aluminum wire.

How does the trip unit operate on the LCP36300MT?

It features a thermal-magnetic trip unit with fixed thermal protection for overloads and an adjustable magnetic setting. This allows you to fine-tune the instantaneous short-circuit response for your specific load.

Can this breaker be used in DC electrical systems?

Yes, in addition to its standard AC ratings, this breaker is rated for 250VDC applications with a 10kA interrupting capacity.

Is this a plug-on or bolt-on circuit breaker?

The LCP36300MT is a bolt-on breaker. It requires bolted connections for installation and is not compatible with plug-on panelboard systems.

Is the LCP36300MT still actively manufactured?

This model is part of the legacy L-Frame series. It is typically used as a direct replacement to maintain existing switchboards and motor control centers without requiring a complete system upgrade.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.