Part of the PowerPacT L-Frame series, this 600A breaker provides advanced LSI coordination via its integrated MicroLogic 3.3S trip unit. It mounts into standard I-Line panelboards and switchboards, serving as a modern replacement for legacy LC36600 and LI36600 models. With a robust 100kA interrupting rating at 480VAC, it ensures reliable current-limiting performance for demanding commercial and industrial electrical distribution systems.
Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Rotary Handle, Communication Module
Accessories
MicroLogic 3.3S Trip Unit, Lugs
Standards
CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval
CCC, CE, CSA, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
Current Limiting, HACR Rated, True RMS Sensing, 80% Rated
Product FAQs
8 answers
What panelboards are compatible with the LLA36600U33X breaker?
This breaker is designed exclusively for Square D I-Line panelboards and switchboards. The "A" in the LLA prefix indicates it features an I-Line style plug-in connection on the line side.
How do I decode the LLA prefix on this circuit breaker?
The first "L" indicates the PowerPacT L-Frame. The second "L" denotes the interrupting rating tier (125kA at 240VAC, 100kA at 480VAC, 50kA at 600VAC). The "A" specifies an I-Line plug-in connection.
What trip unit is included with the LLA36600U33X?
The "U33X" suffix indicates this breaker is equipped with a Micrologic 3.3S electronic trip unit. This solid-state trip unit provides adjustable Long-Time, Short-Time, and Instantaneous (LSI) protection for advanced system coordination.
What wire sizes do the load-side lugs on the LLA36600U33X accept?
The standard mechanical lugs on this 600A breaker accept two 2/0 AWG to 500 kcmil aluminum or copper (Al/Cu) conductors per phase.
How is the LLA36600U33X installed in an electrical panel?
It features an I-Line plug-in connection on the line side that mounts directly onto the panelboard bus, while the load side uses traditional mechanical lugs for wire termination.
Can the LLA36600U33X replace older Square D 600A breakers?
Yes, PowerPacT L-Frame breakers like the LLA36600U33X serve as modern replacements for legacy Square D LC and LI frame breakers, such as the LC36600 and LI36600, in I-Line panels. Always verify physical space and busbar requirements before upgrading.
Is the LLA36600U33X rated for 80% or 100% continuous current?
The LLA36600U33X is a standard-rated breaker, meaning it is rated for 80% continuous current. It is not designed to carry its full 600A rating continuously for more than three hours.
Does the LLA36600U33X include ground fault protection?
No, the integrated Micrologic 3.3S trip unit provides LSI (Long-Time, Short-Time, Instantaneous) protection only. If your application requires equipment ground fault protection, you will need a breaker with an LSIG trip unit, such as a Micrologic 6.3.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.