Featuring an integrated ammeter, the PGL36060U43A is a 600-amp, three-pole PowerPacT P-Frame circuit breaker built for demanding industrial environments. It is designed for unit-mount installation in Square D QED switchboards, Model 6 motor control centers, and compatible enclosures. This standard 80% rated MCCB stands out with its factory-installed Micrologic 5.0A trip unit, which provides adjustable LSI protection along with real-time current monitoring and system diagnostics.
What does the U43A suffix indicate on the PGL36060U43A circuit breaker?
The U43A suffix specifies that the breaker is equipped with a Micrologic 5.0 A electronic trip unit. This provides Long-Time, Short-Time, and Instantaneous (LSI) trip functions, along with an integrated ammeter for real-time current monitoring.
Is the PGL36060U43A a standard or 100 percent rated circuit breaker?
This breaker is standard 80 percent rated for continuous current.
Does the PGL36060U43A mount directly to an I-Line panelboard bus?
No, the L in the PGL prefix indicates it is a unit-mount breaker with mechanical lugs on both the line and load sides. For an I-Line plug-on connection, a PGA-prefix breaker is required.
Can the Micrologic trip unit on this P-Frame breaker be swapped in the field?
Yes, PowerPacT P-Frame breakers equipped with Micrologic trip units allow the trip unit to be interchanged in the field. This provides flexibility to upgrade functionality, such as adding advanced power metering or communication capabilities, without replacing the entire breaker frame.
Does this breaker provide ground fault protection?
No, the Micrologic 5.0 A trip unit provides Long-Time, Short-Time, and Instantaneous (LSI) protection only. Equipment ground fault protection requires a Micrologic 6.0 trip unit.
Does the PGL36060U43A support Zone-Selective Interlocking (ZSI)?
Yes, the Micrologic 5.0 A trip unit includes short-time Zone-Selective Interlocking (ZSI) capability. This feature allows the breaker to communicate with downstream devices to improve system coordination and reduce fault clearing times.
Can a motor operator be added in the field to the PGL36060U43A for remote operation?
No, electrically operated P-Frame circuit breakers require a factory-installed motor assembly. Motor-operated versions are denoted by an M suffix in the catalog number and cannot be retrofitted in the field to a standard manually operated breaker.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.