Providing robust overcurrent defense, the Square D QJA221504 is a 150A thermal-magnetic circuit breaker from the PowerPacT Q-Frame family. This device is engineered to plug into Square D I-Line panelboards and switchboards. It also functions as an exact substitute for discontinued Q22150 breakers. Featuring a 100 kAIC rating at 240VAC, this two-pole MCCB comes with a factory-configured BC phase connection, fixed LI trip functions, and a highly visible Visi-Trip indicator.
CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, NOM-003-SCFI-2000, UL 489
Approval
ANCE, CSA, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Visual Trip Indicator
Product FAQs
8 answers
What panelboards are compatible with the QJA221504 circuit breaker?
This breaker is designed exclusively for Square D I-Line panelboards and switchboards. It will not fit in standard QO, Homeline, or NQ/NF series panels.
What does the "4" suffix in the QJA221504 catalog number indicate?
In Square D I-Line nomenclature, the "4" suffix indicates that this 2-pole breaker is factory-configured for a BC phase connection on the panelboard busbar.
What does the "J" in the QJA221504 catalog number indicate?
In the PowerPacT Q-Frame nomenclature, the "J" designates the interrupting rating tier. It signifies a high interrupting capacity of 100kA at 240VAC.
Are the trip settings on the QJA221504 adjustable?
No, this breaker features a fixed thermal-magnetic trip unit. Both the Long-Time (thermal) and Instantaneous (magnetic) trip functions are factory-set and cannot be adjusted in the field.
Can the QJA221504 replace older Square D Q2 series breakers?
Yes, Schneider Electric designed the PowerPacT Q-Frame circuit breakers as direct replacements for legacy Square D Q2 Series devices, provided the pole count, amperage, and mounting style match.
How is the QJA221504 breaker secured to the I-Line busbar?
The breaker features a plug-on line-side jaw connection. During installation, the integrated mounting bracket hooks into the panel pan, and a retaining screw is tightened to secure the breaker firmly against the busbar stack.
Does the QJA221504 require line-side wiring?
No. Because it is an I-Line breaker, the line side connects directly to the panelboard busbar via plug-on jaws. Only the load side requires wire termination using the provided mechanical lugs.
What safety precautions are required when installing this I-Line breaker?
Always de-energize the panelboard before installation. Ensure the breaker is in the OFF position, align the mounting bracket with the pan slots, and use a screwdriver to ratchet the breaker onto the busbar stack smoothly without forcing it.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.