Engineered for heavy-duty use, the Square D PKL36060CU31A is a 600A, 3-pole PowerPacT P-Frame circuit breaker. It is 100% rated to handle continuous current loads. The unit-mount design installs into Square D switchboards, motor control centers, and P-Frame enclosures. It features lug terminals for up to 500 kcmil wire. It includes a MicroLogic 3.0 trip unit for adjustable long-time and instantaneous (LI) protection. The breaker provides true RMS sensing and a 50kAIC rating at 480VAC.
Is the PKL36060CU31A rated for 100 percent continuous current?
Yes. The "C" in the catalog number indicates this breaker is 100 percent rated. This allows it to carry its full 600A capacity continuously when installed in a properly sized and ventilated enclosure, rather than the standard 80 percent limit.
What adjustability does the Micrologic 3.0 trip unit provide?
The Micrologic 3.0 (U31A) electronic trip unit features adjustable Long-Time and Instantaneous (LI) settings. It includes a Type A rating plug, allowing the long-time pickup to be dialed from 0.4 to 1.0 times the 600A sensor rating, which translates to an adjustable range of 240A to 600A.
Where can the PKL36060CU31A be installed?
This unit-mount, feed-thru breaker is designed for installation in Square D switchboards, motor control centers, and dedicated PowerPacT P-Frame enclosures. It is not compatible with I-Line panelboards, which require a plug-on mounting configuration.
What are the lug requirements for this breaker?
The factory-installed lugs on both the line and load sides accept three 3/0 AWG to 500 kcmil aluminum or copper conductors per phase. Installers must ensure the enclosure provides adequate wire bending space for parallel 500 kcmil conductors.
Can this breaker replace an older Square D 600A P-Frame?
Yes, the PKL36060CU31A is a direct replacement for older unit-mount PowerPacT P-Frame breakers with the same K-class interrupting rating and LI trip functions. Verify that your existing setup uses unit mounting rather than I-Line plug-on connections before replacing.
Does this breaker provide ground fault protection?
No. The Micrologic 3.0 trip unit provides Long-Time and Instantaneous (LI) protection only. It does not include Short-Time or Ground Fault protection. If equipment ground fault protection is required by code, a breaker with a Micrologic 6.0 (LSIG) trip unit is necessary.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.