Skip to main content

ABB S3N030TW Molded Case Circuit Breaker

  • 30A
  • 3 Pole
  • Unit Mount
ABB S3N030TW
Molded Case Circuit Breaker
Brand ABB
SKU S3N030TW
Select Item Condition
Earn 395 SuperPoints
  • 30A
  • 3 Pole
  • Unit Mount

Quantity

Bulk Pricing
Send your parts list for a volume quote.
ABB S3N030TW 3 Pole Circuit Breaker

ABB S3N030TW - 30A 3 Pole Molded Case Circuit Breaker

New

$395.48 No Stock

Quantity

Description

Built for commercial and industrial power distribution, this 30-amp Isomax S3 breaker features fixed thermal and magnetic trip elements. It provides reliable long-time and instantaneous protection for complex electrical systems. Designed to mount into ABB panelboards and motor control centers, it is a reverse-feed capable unit. While it has been superseded by the T3N030TW, this exact match maintains compatibility with existing Isomax infrastructure.

Specifications

Key specifications
Brand ABB
Part Number S3N030TW
Series Isomax S3
Amperage 30A
Poles 3
Mounting Style Unit Mount
Voltage 240VAC, 480VAC, 600VAC, 500VDC
Phase 3
AIC Rating 65kA @ 240VAC, 25kA @ 480VAC, 14kA @ 600VAC, 25kA @ 500VDC
Fit and installation
Terminal Type Lugs
For Use With ABB Panelboards, Switchboards, Motor Control Centers
Wire Gauge 14-2 AWG
Max Wire 2 AWG
Min Wire 14 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Fixed Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm, Lug Kits
Accessories Lugs Not Included
Standards CSA C22.2 No. 5, IEC 60947-2, UL 489
Approval CSA, IEC, UL
Temp Rating 40C
Construction Features HACR Rated, Reverse Feed, Non-Interchangeable Trip

Product FAQs

7 answers
What is the direct replacement for the legacy ABB S3N030TW?

The S3N030TW is part of the legacy Isomax S3 family and has been superseded by the Tmax series T3N030TW. Using the original S3N030TW allows you to maintain exact physical and electrical compatibility with existing Isomax infrastructure without retrofitting.

Is the S3N030TW suitable for reverse feed applications?

Yes, all circuit breakers in the ABB Isomax S3 family, including the S3N030TW, are reverse-feed capable.

How are internal accessories configured in the Isomax S3 frame?

Internal accessories are field-installable. Shunt trips and undervoltage releases (UVR) must be mounted in the left accessory cavity, while auxiliary contacts and bell alarm switches are installed in the right cavity.

Where can the S3N030TW be installed?

This unit-mount, bolt-on breaker is designed for installation in ABB panelboards, switchboards, and motor control centers configured for the Isomax S3 frame.

Can the trip settings on the S3N030TW be adjusted in the field?

No, this breaker is equipped with a non-interchangeable thermal-magnetic trip unit. Both the long-time (thermal) and instantaneous (magnetic) trip functions are fixed at the factory for 30A protection.

Can this breaker be used in DC power systems?

Yes, the S3N030TW is rated for DC applications up to 500VDC, providing a 25kA interrupting capacity for DC circuits.

What is the maximum amperage capacity of the Isomax S3 frame?

While the S3N030TW is configured for 30A, the ABB Isomax S3 frame itself supports breaker configurations ranging from 15A up to a maximum of 225A.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.