Operating within the XT1 frame, the ABB XT1NU3125AAA000XXX is a 3-pole, 125A molded case circuit breaker. It provides essential power distribution and circuit protection for demanding commercial and industrial environments. This unit mount MCCB installs into ABB SACE Tmax XT panelboards, switchboards, and enclosures. It is an exact drop-in replacement for discontinued Tmax T1 series breakers. Rated 25kAIC at 480VAC, it features a fixed thermal magnetic trip unit and includes terminal lugs.
Can this 3-pole XT1 breaker be used in single-phase applications?
Yes, ABB XT1 three-pole circuit breakers can be used in single-phase applications. According to UL standards, they are marked as suitable for single-phase applications up to 347VAC.
Is the ABB XT1NU3125AAA000XXX suitable for reverse feeding?
Yes, power can be supplied to the bottom terminals of the XT1 breaker up to its maximum voltage rating without compromising its protective capabilities.
What is the ambient operating temperature range for this breaker?
Tmax XT circuit breakers are designed to operate in ambient air temperatures ranging from -25 degrees Celsius to +70 degrees Celsius. The reference temperature for the thermal magnetic trip unit is +40 degrees Celsius.
Can the XT1NU3125AAA000XXX replace older ABB Tmax T1 breakers?
Yes, the XT1 frame is designed as a direct drop-in replacement for the discontinued ABB SACE Tmax T1 series breakers, fitting the same panelboards and enclosures.
What does the N signify in the XT1N frame designation?
The N indicates a Normal interrupting capacity for the XT1 frame, which provides a maximum interrupting rating of 25kA at 480VAC and 50kA at 240VAC.
What type of trip unit is installed in the XT1NU3125AAA000XXX?
This breaker features a Thermal Magnetic Fixed (TMF) trip unit. Both the long-time (thermal) and instantaneous (magnetic) trip functions are fixed and non-adjustable.
What equipment is compatible with the XT1NU3125AAA000XXX?
This unit mount molded case circuit breaker is designed for installation in ABB SACE Tmax XT panelboards, switchboards, and compatible industrial enclosures.
Does this breaker provide ground fault protection?
No, this breaker is equipped with an LI (Long-Time, Instantaneous) trip unit. It provides overload and short circuit protection, but does not include integrated ground fault protection.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.