| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | EGB3090FFG |
| Series | EGB |
| Amperage | 90A |
| Poles | 3 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 250VDC |
| Phase | 3 |
| AIC Rating | 25kA @ 240VAC, 18kA @ 480VAC, 10kA @ 250VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | Eaton Series G Enclosures, Switchboards, MCCs, Pow-R-Line Panelboards |
| Wire Gauge | 14-1/0 AWG |
| Max Wire | 1/0 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Handle Mechanism |
|---|---|
| Accessories | Line and Load Terminals |
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489 |
| Approval | CE, CSA, IEC, KEMA, UL |
| Temp Rating | 40C |
| Construction Features | Current Limiting, HACR Rated, Reverse Feed |
No, this is an industrial molded case circuit breaker. It is specifically designed for Eaton Pow-R-Line panelboards, Series G enclosures, switchboards, and MCCs, rather than residential load centers.
Yes, the legacy Series G EGB3090FFG has been replaced by the Eaton Power Defense PDG13C0090TFFJ. The newer Frame 1 breaker serves as an exact drop-in replacement for the older EG-frame model.
Yes, the factory-installed line and load lugs are rated for both copper and aluminum (Cu/Al) conductors ranging from 14 AWG to 1/0 AWG.
Unit mount, also known as cable-in/cable-out or bolt-on mounting, means the breaker is individually mounted to the enclosure backpan using screws or bolts, rather than plugging directly into a distribution busbar.
Yes, this Series G molded case circuit breaker is reverse feed capable, allowing you to connect the incoming power to either the top or bottom terminals.
The thermal element provides delayed tripping for sustained overloads, while the magnetic element delivers an instantaneous trip response to clear severe short circuits.
Yes, the EG-frame supports various internal accessories, including shunt trips, undervoltage releases, auxiliary switches, and alarm contacts, which install directly into the breaker.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.