Eaton/Cutler-Hammer FD3200L 3 Pole Circuit Breaker
The Eaton/Cutler-Hammer FD3200L is a 3 Pole thermal magnetic molded case circuit breaker with a current rating of 200 Amps and a voltage rating of 600VAC, 250VDC. It has an interrupting rating of 35kAIC at 480VAC, 65kAIC at 240VAC. The FD3200L has a feed-thru connection type and includes long time and instantaneous trip functions.
What panelboards are compatible with the FD3200L circuit breaker?
The FD3200L is a Series C F-frame breaker designed for use in Eaton, Cutler-Hammer, and Westinghouse panelboards, switchboards, and enclosures. It is commonly installed in Pow-R-Line 3a (PRL3a) and Pow-R-Line 4 (PRL4) distribution panels.
Does the FD3200L include line and load lugs?
Yes, the L suffix in the FD3200L catalog number indicates that standard line and load lugs are included. These factory-installed terminals accept 4 AWG to 4/0 AWG copper or aluminum conductors.
What is the difference between Eaton FD, HFD, and FDC circuit breakers?
These prefixes indicate the interrupting capacity of the Series C F-frame breakers at 480VAC. The FD3200L is the standard tier rated at 35kAIC. The HFD is the high-interrupting version rated at 65kAIC, and the FDC is the current-limiting version rated at 100kAIC. All three share the same physical footprint.
Is this breaker a direct replacement for older Westinghouse FD3200L models?
Yes. Eaton manufactures the Series C line, which was formerly branded under Cutler-Hammer and Westinghouse. A new Eaton FD3200L is an exact drop-in replacement for legacy Westinghouse or Cutler-Hammer breakers with the same catalog number.
Can I field-install internal accessories like a shunt trip in the FD3200L?
While the FD3200L supports internal accessories such as shunt trips, auxiliary contacts, and undervoltage releases, Eaton requires these to be factory-installed. Field installation of internal accessories in Series C F-frame breakers voids the UL listing.
Can the FD3200L be reverse fed?
Yes, this thermal-magnetic breaker is suitable for reverse feed applications. It does not have restrictive line and load markings, allowing power to be supplied from either the top or bottom terminals.
Are the trip settings adjustable on the FD3200L?
No, the FD3200L features a fixed thermal-magnetic trip unit. Both the long-time overload and instantaneous short-circuit trip functions are factory set and cannot be adjusted in the field.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.