Serving as a reliable power distribution component, this 20A F-Frame breaker handles commercial and industrial loads up to 600VAC. The unit mounts into Eaton Series C and legacy Westinghouse panelboards, switchboards, and motor control centers. While Eaton has introduced the Power Defense PDG23F0020TFFJ as a modern substitute, this original FDB model maintains native compatibility without requiring specialized retrofit kits for existing installations.
What equipment is compatible with the FDB3020 circuit breaker?
This F-Frame breaker is designed for use in Eaton Series C panelboards, legacy Westinghouse panelboards, switchboards, and motor control centers.
Can the Eaton FDB3020 replace an older Westinghouse FDB3020?
Yes. Eaton acquired the distribution equipment division of Westinghouse, so the Eaton FDB3020 is a direct, native replacement for the original Westinghouse FDB3020 without requiring specialized retrofit kits.
Does the FDB3020 come with both line and load lugs?
No. The standard FDB3020 catalog number includes load-side lugs only. If you need both line and load lugs, you will need the FDB3020L variant or must purchase line lugs separately.
What wire size and material does the FDB3020 accept?
The standard load lugs accept 14 AWG to 1/0 AWG copper or aluminum wire.
Is the FDB3020 suitable for reverse feed applications?
Yes. Like most Eaton Series C F-Frame breakers, the FDB3020 is reverse feed capable, making it versatile for various power distribution setups.
Is this breaker HACR rated?
Yes, the FDB3020 is HACR rated, meaning it is approved for use with heating, air conditioning, and refrigeration equipment.
What is the difference between the FDB3020 and the FD3020?
Both are 20A, 3-pole F-Frame breakers, but they have different interrupting capacities. The FDB3020 is the standard-tier breaker rated at 14 kAIC at 480VAC, while the FD3020 is a higher-tier breaker rated at 35 kAIC at 480VAC.
Are the trip settings adjustable on the FDB3020?
No. This breaker features a fixed thermal and fixed magnetic trip unit, meaning the overload and short-circuit trip thresholds cannot be adjusted in the field.
What is the difference between the FDB3020 and the EHD3020?
While both are 20A, 3-pole F-Frame breakers with a 14 kAIC rating at 480VAC, the EHD3020 is rated for a maximum of 480VAC. The FDB3020 is rated for up to 600VAC.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 2 reviews.