Rated for 30A, the Eaton FDC3030L is a high-performance molded case circuit breaker from the Series C F-Frame lineup. It delivers reliable long-time and instantaneous trip functions for industrial systems. This unit mount breaker is compatible with Eaton Pow-R-Line 1a, 2a, and 3a panelboards. The "L" suffix indicates it comes factory-equipped with both line and load side lugs for immediate wiring. With an interrupting capacity of 200kAIC at 240V, it offers superior current limiting protection.
Current Limiting, HACR Rated, Non-Interchangeable Trip
Product FAQs
8 answers
What is the difference between the FD3030L, HFD3030L, and FDC3030L?
These breakers share the same physical F-frame footprint and 30A trip curve but have different interrupting ratings. The FD3030L is rated for 35kA at 480V, the HFD3030L is rated for 65kA, and the FDC3030L offers the highest protection in this class at 100kA.
Can the FDC3030L replace older Westinghouse FDC breakers?
Yes. Eaton acquired the Westinghouse molded case circuit breaker line. The modern Eaton or Cutler-Hammer Series C FDC3030L is a direct drop-in replacement for legacy Westinghouse breakers with the exact same catalog number.
What does the L suffix mean in the FDC3030L catalog number?
The L indicates that the breaker comes factory-equipped with standard line and load side lugs. These terminals are designed to accept 14 to 1/0 AWG copper or aluminum wire.
How is this breaker mounted in a panelboard?
The FDC3030L is a unit mount, or feed-thru, breaker. It bolts directly to the chassis or mounting pan rather than plugging onto a busbar, making it suitable for Eaton Pow-R-Line panelboards, switchboards, and motor control centers.
Does the FDC3030L include adjustable trip settings?
No. This specific model features a fixed thermal and fixed magnetic trip unit. It provides standard long-time and instantaneous protection without adjustable dials.
Is this breaker suitable for direct current applications?
Yes, the FDC3030L is rated for up to 250VDC with an interrupting capacity of 22kA. When installing in DC systems, consult Eaton technical documentation to ensure proper pole wiring configurations.
Are accessories like shunt trips or auxiliary switches field-installable on the FDC3030L?
Yes, Eaton Series C F-frame breakers support a variety of internal accessories. They must be installed in the designated accessory pockets located under the front cover, following Eaton guidelines for field installation.
Can I use this breaker as a main disconnect?
Yes, provided the enclosure and system design accommodate a 30A unit mount breaker. It is commonly used as a main or branch device in Series C switchboards and compatible motor control centers.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 2 reviews.