Cutler-Hammer / Westinghouse L3400 3 Pole Circuit Breaker

Eaton / Cutler-Hammer L3400 - 400A 3 Pole Molded Case Circuit Breaker

Re-Certified

$835.88 In Stock

Quantity

Description

Operating as a critical safety device, the Eaton L3400 is a 3-pole, 400A legacy circuit breaker. It safeguards heavy industrial loads against damaging short circuits. This breaker mounts securely into vintage Cutler-Hammer and Westinghouse panelboards. Professionals should note this PB Frame unit is replaced by the newer LD3400 model. The device utilizes a reliable thermal-magnetic trip mechanism with adjustable magnetic capabilities. It provides a 35 kAIC interrupting capacity at 480VAC.

Specifications

Key specifications
Brand Eaton / Cutler-Hammer
Part Number L3400-R
Series L
Amperage 400A
Poles 3
Mounting Style Unit Mount
Voltage 240VAC, 480VAC, 600VAC, 250VDC
Phase 3
AIC Rating 65kA @ 240VAC, 35kA @ 480VAC, 25kA @ 600VAC, 22kA @ 250VDC
Fit and installation
Terminal Type Lugs
For Use With Westinghouse Panelboards, Cutler-Hammer Panelboards, Switchboards, Motor Control Centers
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Adjustable Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch
Accessories Line and Load Lugs Included
Standards CSA C22.2 No. 5, NEMA AB 1, UL 489
Approval CSA, UL
Temp Rating 40C
Construction Features Interchangeable Trip Unit, HACR Rated

Product FAQs

8 answers
Is there a modern replacement for the legacy L3400 circuit breaker?

Yes. The L3400 is a legacy PB Frame breaker originally manufactured by Westinghouse and Cutler-Hammer. For modern panel upgrades, it is typically replaced by the newer Eaton Series C LD3400 model.

Which legacy panelboards will accept the L3400 breaker?

This unit is a direct fit for vintage Westinghouse and Cutler-Hammer panelboards, switchboards, and motor control centers that require a PB Frame footprint.

How is the thermal-magnetic trip unit configured on the L3400?

The breaker utilizes an LI (Long-Time, Instantaneous) trip function. The thermal element is fixed for standard overload protection, while the magnetic instantaneous trip is adjustable to coordinate with specific short-circuit fault levels.

What does the unit mount designation mean for installation?

As a unit-mount breaker, the L3400 bolts directly to the backpan or chassis of the enclosure and requires hardwired cable connections at both the line and load lugs, rather than plugging directly onto a busbar.

What is the short-circuit interrupting capacity of this breaker in 480V systems?

The L3400 is rated to safely interrupt up to 35,000 amps (35 kAIC) during a fault in a 480VAC system.

Is the L3400 suitable for direct current applications?

Yes, it is rated for DC systems up to 250VDC, providing a maximum interrupting capacity of 22 kAIC for DC loads.

Can the trip unit on the L3400 be swapped out?

Yes, this breaker features an interchangeable trip unit design. This allows electricians to replace or upgrade the trip mechanism without having to remove the entire breaker frame from the panel.

Does the L3400 carry a HACR rating?

Yes, this breaker is HACR rated, meaning it is certified for use with heating, air conditioning, and refrigeration equipment that requires specialized short-circuit and overload protection.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.

Reviews

5.0
Rated 5.0 out of 5 stars
Based on 1 review
Total 5 star reviews: 1 Total 4 star reviews: 0 Total 3 star reviews: 0 Total 2 star reviews: 0 Total 1 star reviews: 0
Rating
Ratings
1 review
  • JH
    Joel H.
    Flag of United States
    Reviewing
    Westinghouse L56D Contact Block
    I recommend this product
    Rated 5 out of 5 stars
    2/28/18
    Owner

    Product was exactly as described, will use again in the future.