Built for heavy-duty industrial applications, the Eaton NGH312033E is a 1200A, 3-pole MCCB from the Series G lineup. It provides robust power distribution when mounted into Pow-R-Line 4 panelboards, switchboards, or motor control centers. This standard 80% rated bolt-on breaker serves as a reliable component for existing infrastructure and is replaced by the PDG53M1200E2NN. Equipped with an adjustable LS electronic trip unit, it offers a 65 kAIC rating at 480V and reverse-feed capabilities.
Does the NGH312033E include lugs for wire termination?
No, this breaker is supplied with standard imperial tapped line and load pads. If you need to terminate cables, compatible lug kits must be purchased separately. Common options include the TA1200NB1 kit for four 4/0 to 500 kcmil conductors per phase, or the TA1201NB1 kit for three 500 to 750 kcmil conductors.
What protection settings are adjustable on the NGH312033E?
The "33" suffix signifies a Digitrip 310+ electronic trip unit with adjustable Long-Time and Short-Time (LS) protection. The Short-Time delay utilizes an I2t response curve. While it has a fixed instantaneous override for self-protection at extremely high fault levels, it does not feature user-adjustable instantaneous or ground fault settings.
Is the NGH312033E a 100% rated circuit breaker?
No, this is a standard 80% rated circuit breaker. For continuous loads lasting three hours or more, the continuous current should not exceed 80% of its 1200A frame capacity (960 amps). Eaton designates 100% rated breakers in this series with a "C" suffix in the catalog number.
Is the NGH312033E suitable for reverse feed applications?
Yes, Eaton NG-frame electronic molded case circuit breakers are suitable for reverse feed use. They can be wired with the line or load connections on either side without compromising the performance of the Digitrip 310+ protection system.
What is the difference between the NGH312033E and NGH312033M?
The "E" suffix on the NGH312033E indicates it is equipped with imperial tapped line and load conductors. The "M" suffix indicates metric tapped conductors. Both are 1200A, 3-pole NG-frame breakers with identical electrical ratings.
Can the trip unit on the NGH312033E be field tested for proper coordination?
Yes, the Digitrip RMS 310+ electronic trip unit features a built-in test port. Electricians can use an Eaton portable test kit to run functional tests on the Long-Time and Short-Time protection circuits without needing to pass primary current through the breaker.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.